
| MSS User Guide | 4: Configuration | 
line is available to receive again. At most baud rate settings, the timing delay is typically one character length with a maximum of 1.5 character lengths.
Note: For 600 baud and 4800 baud operation, the timing delay is doubled.
Figure 4-22:  Enabling Two-Wire  RS-485  Mode for MSS4
 Local> CHANGE RS485 PORT 2 MODE 2WIRE
 Local> CHANGE RS485 PORT 2 MODE 2WIRE 
Figure 4-23:  Enabling Two-Wire  RS-485  Mode for MSS-VIA 
 Local> CHANGE RS485 MODE 2WIRE
 Local> CHANGE RS485 MODE 2WIRE 
Note: For 
Four-Wire  Mode
In 
Figure 4-24.  Example Four-Wire  Mode Network
It is important to connect the transmitter of the master device to the wire that is connected to the receive terminals on the slave devices, and connect the receiver of the master device to the wire that is connected to the transmit terminals on the slave devices. In essence, the master device will be connected to the slave devices with a swapped cable.
In 
Figure 4-25:  Enabling Four-Wire  RS-485  Mode for MSS4
 Local> CHANGE RS485 PORT 2 MODE 4WIRE
 Local> CHANGE RS485 PORT 2 MODE 4WIRE 
Figure 4-26:  Enabling Four-Wire  RS-485  Mode for MSS-VIA 
 Local> CHANGE RS485 MODE 4WIRE
 Local> CHANGE RS485 MODE 4WIRE