Magnum 6KQE Managed Edge Switch Installation and User Guide | 02/09 |
When power is applied, the green PWR LED will illuminate.
Note: The GND should be hooked up first. The 6KQE unit has a floating ground, so the user may elect to Ground either + or - terminal to suit the customer’s use.
Before connecting live power lines to the Terminal Block of
B4.1 UL Requirements for DC-powered units
CAUTION: 48VDC products shall be installed with a readily accessible disconnect device in the building installation supply circuit to the product.
Minimum 18AWG cable for connection to a Centralized DC power source.
1.Minimum 14AWG cable for connection to an earth wiring.
2.Use only with Listed 10A circuit breaker provided in building installation.
3.“Complies with FDA radiation performance standards, 21 CFR subchapter J.” or equivalent.
4.Fastening torque of the lugs on the terminal block: 9
5.To secure a centralized DC Power Source cable , use at least four cable ties to secure the cable to the rack at least 4 inches apart, with the first one located within 6 inches of the terminal block.
B5.0 OPERATION
Operation of Magnum 6KQE Switches with the optional
B6.0 TROUBLESHOOTING
Please refer to Section 6.0 for troubleshooting