GE GEK 106168E manual Communications, Standards, Test Standard Class

Page 30

4. TECHNICAL CHARACTERISTICS

COMMUNICATIONS

-RS232 using DB9 female connector (2/3 connectors depending on model)

- Mode: Half duplex

-1 mm plastic fiber-optic (depending on model)

Typical power output :

-8dBm

Receiver sensitivity

-39dBm

Numeric aperture N.A.

0.5

Wave length

660 nm (visible red)

HFBR-4516 type connector

 

-Glass fiber-optic 62.5/125 (depending on model):

Typical power output:

-17.5 dBm

Receiver sensitivity

-25.4 dBm

Numeric aperture N.A.

0.2

Wave length

820 nm (near infrared)

SMA type connector

 

STANDARDS

The DBF system complies with the following standards, which include the GE insulation and electromagnetic compatibility standard and the standards required by Community Directive 89/336 for the EC market, in line with European standards. It also complies with the European directive requirements for low voltage, and the environmental and operating requirements established in ANSI standards C37.90, IEC 60255-5, IEC 60255-6 and IEC 68.

Test

Standard

Class

Insulation test voltage

IEC 60255-5

600V, 2kV

 

50/60 Hz 1 min.

 

Impulse voltage

IEC 60255-5

5kV,0.5 J

1 MHz interference

IEC 60255-22-1

III

Electrostatic discharge

IEC 60255-22-2

IV

 

EN 61000-4-2

8kV

Immunity to radio interference

IEC 60255-22-3

III

•Electromagnetic fields radiated with

ENV 50140

10 V/m

amplitude modulation

 

 

•Electromagnetic fields radiated with

ENV 50141

10 V/m

amplitude modulation. Common mode

 

 

•Electromagnetic fields radiated with

ENV 50204

10 V/m

frequency modulation

 

 

•Fast transients

IEC 60255-22-4

IV

 

EN 61000-4-4

 

•Magnetic fields at industrial

EN 61000-4-8

30 Av/m

frequency

 

 

•RF emission

EN 55011

B

GEK-106168E

DBF Breaker Failure Protection

23

Image 30
Contents GE Power Management 3KRQHHVFULSWLRQ0DQXDO*RI.\RXUFRGHTXHVWLRQ Ruvxjjhvwlrqd Page Table of Contents Installation and Maintenance List of Figures Rear View 226B7412 SheetDBF Breaker Failure Protection GEK-106168E ∙ Breaker internal arc detection Monitoring General DescriptionProtection AnalysisDBF Breaker Failure Protection GEK-106168E Overcurrent Units Digital Signal Input # TerminalsProtection Functions Low-Level Overcurrent Breaker Failure Unit 50BF 1PBreaker Failure without current or very low current Reset of Latching RelaysGround Overcurrent Breaker Failure Unit Breaker Arc Detection DeviceMeasurement Internal Protection Status SignalsMonitoring and Recording Functions Associated Breaker StatusGroup Status Comment Optional Exp. Board Optional Exp. Board Latched#1 ClosedOptional Exp.Boar Latched#2 Closed Internal Communication Status Signals LED Left Column Right Column Circuit Breaker Breaking Capacity MonitoringEvent Recorder Analysis FunctionsBUILT-IN SELF-CHECKING Unit OscillographyEvents to Trigger Oscillography Table Selection Active Table Tables of SettingsControl INPUT-1 INPUT-0Configurable Inputs and Outputs Time SynchronizationFunction Outputs MAN-MACHINE Interface HMI Remote Communications Breaker Setting Group Active table setting groupInternal Arc Settings Common to all tables Range Default Step Oscillography MaskIndependent for each table Range Default Step 50BF Settings Functions PermittedComments on Settings DBF Breaker Failure Protection GEK-106168E DBF Ranges Models DBF PhaseModel List GroundTechnical Characteristics MechanicalElectrical Communications StandardsTest Standard Class DBF Breaker Failure Protection GEK-106168E Electrical Connections Physical DescriptionCase Internal ConstructionDBF Breaker Failure Protection GEK-106168E Operating Theory Magnetic ModuleCPU Board Power Supply Keyboard and DisplayConnections and Necessary Equipment Visual InspectionPanel Insulation Tests Relay Setting IndicatorsPower Supply Communications Inputs Digital InputsIRIG-B Synchronizing Input Functions 1 50BF 1P Unit Test2 50BF 3P Unit Test Internal ARC Test 4 3P no I FunctionNeutral Overcurrent Unit Test DBF Breaker Failure Protection GEK-106168E Relay Measurement Tests Current MeasurementTiming Measurement DBF Breaker Failure Protection GEK-106168E Installation MaintenanceCONNECTION-TO-GROUND and Disturbances Suppression DBF Breaker Failure Protection GEK-106168E Keyboard and Display DBF General ElectricINF Menu TreeSET ACTModify Settings Protection Settings Group SET KEYView Settings Protection View Protection SettingsConfirm Setting OUT Range Level Valid RangeInformation Group INF KEY StatusControl Group ACT KEY SET DATE/TIMESingle KEY Menu Configuration Menu DBF Breaker Failure Protection GEK-106168E Figures Breaker Failure Logic 189C4114 Sheet External Connections 189C4114 Sheet Front View 226B7412 H9 Rear View 226B7412H10 Dimensions Diagram 226B6086H10 Panel Drilling 226B6086H10 RS232 Connection DBF Relay to PC