| 1. GENERAL DESCRIPTION AND APPLICATION |
1. | GENERAL DESCRIPTION AND APPLICATION |
|
|
1.1. GENERAL DESCRIPTION
The DBF system is a microprocessor based breaker failure protection, control and measurement unit that has different algorithms to allow its use on a wide range of applications in power systems.
The functions and information management of the unit can be performed remotely (computer connected to the serial port RS232,
The system provides the following functions:
a)Protection
∙Low current level breaker failure protection, following a single or three phases initiation, with up to two time delayed steps.
∙High current level breaker failure protection, following a two/three (selectable by setting) phases initiation.
∙No current breaker failure protection, following a two/three (selectable by setting) phases initiation.
∙Breaker internal arc detection.
b)Monitoring
∙Current measurements for each phase and ground.
∙Breaker status
∙16 fully configurable LED indicators
∙One fixed relay status LED
∙Breaker health monitoring (ΣI2 t).
∙
c)Analysis:
∙Event recorder
∙Oscillography
d)Control:
∙3 settings’ tables
∙Time synchronization using the communications program, the
∙Configurable inputs and outputs.
∙User can build logic schemes using AND, OR and NOT gates and the internal digital signals of the relay.
DBF Breaker Failure Protection | 1 |