2. OPERATION LOGIC

2.4. CONTROL

2.4.1 TABLES OF SETTINGS

The DBF system has two types of settings stored in non-volatile memory (information is kept even when there is no auxiliary voltage):

Generic Settings.

Specific Settings.

The Generic settings are grouped as follows:

GENERAL SETTINGS

BREAKER SETTINGS

ACTIVE TABLE SETTINGS

OSCILLOGRAPHY MASK

FUNCTION PERMISSION

For the specific settings, the DBF allows to have up to 3 independent setting tables. These specific settings are grouped as follows:

50BF SETTINGS INTERNAL ARC SETTINGS

Only one setting table is active at a given time, and this is the table used by the system to run the different functions included in it.

There is an "ACTIVE TABLE" setting that determines the settings table that is active at a given moment.

The active settings table can be changed by means of up to 2 digital inputs, referred to as "ACTIVE TABLE SELECT 0" and "ACTIVE TABLE SELECT 1" which allow up to 4 combinations from 0 to 3. To do this it is necessary to configure (using GE-INTRO software) two inputs to have these meanings. For applications which require less tables (up to 2) it is possible to use only one input.

The selected combination is obtained from the binary coding of the 2 inputs mentioned (see following table). The 0-0 means selecting the table indicated in the "ACTIVE TABLE" setting, and numbers 0-1 to 1-1 select tables 1 to 3 respectively

Table Selection

Table Selection

Active Table

INPUT-1

INPUT-0

 

0

0

Selected by setting

0

1

1

1

0

2

1

1

3

NOTE: if the inputs are programmed and used, energizing them, this selection has priority over the "ACTIVE TABLE" setting and the table which is in fact used is determined by the status of the digital inputs.

12

DBF Breaker Failure Protection

GEK-106168E

Image 19
Contents GE Power Management 3KRQHHVFULSWLRQ0DQXDO*RI.\RXUFRGHTXHVWLRQ Ruvxjjhvwlrqd Page Table of Contents Installation and Maintenance Rear View 226B7412 Sheet List of FiguresDBF Breaker Failure Protection GEK-106168E Analysis General DescriptionProtection ∙ Breaker internal arc detection MonitoringDBF Breaker Failure Protection GEK-106168E Low-Level Overcurrent Breaker Failure Unit 50BF 1P Digital Signal Input # TerminalsProtection Functions Overcurrent UnitsBreaker Arc Detection Device Reset of Latching RelaysGround Overcurrent Breaker Failure Unit Breaker Failure without current or very low currentAssociated Breaker Status Internal Protection Status SignalsMonitoring and Recording Functions MeasurementGroup Status Comment Optional Exp. Board Closed Optional Exp. Board Latched#1Optional Exp.Boar Latched#2 Closed Internal Communication Status Signals Circuit Breaker Breaking Capacity Monitoring LED Left Column Right ColumnOscillography Analysis FunctionsBUILT-IN SELF-CHECKING Unit Event RecorderEvents to Trigger Oscillography INPUT-1 INPUT-0 Tables of SettingsControl Table Selection Active TableTime Synchronization Configurable Inputs and OutputsFunction Outputs MAN-MACHINE Interface HMI Remote Communications Active table setting group Breaker Setting GroupFunctions Permitted Common to all tables Range Default Step Oscillography MaskIndependent for each table Range Default Step 50BF Settings Internal Arc SettingsComments on Settings DBF Breaker Failure Protection GEK-106168E Ground Ranges Models DBF PhaseModel List DBFMechanical Technical CharacteristicsElectrical Standards CommunicationsTest Standard Class DBF Breaker Failure Protection GEK-106168E Internal Construction Physical DescriptionCase Electrical ConnectionsDBF Breaker Failure Protection GEK-106168E Magnetic Module Operating TheoryCPU Board Keyboard and Display Power SupplyVisual Inspection Connections and Necessary EquipmentPanel Insulation Tests Indicators Relay SettingPower Supply Communications Digital Inputs InputsIRIG-B Synchronizing Input 1 50BF 1P Unit Test Functions2 50BF 3P Unit Test 4 3P no I Function Internal ARC TestNeutral Overcurrent Unit Test DBF Breaker Failure Protection GEK-106168E Current Measurement Relay Measurement TestsTiming Measurement DBF Breaker Failure Protection GEK-106168E Maintenance InstallationCONNECTION-TO-GROUND and Disturbances Suppression DBF Breaker Failure Protection GEK-106168E DBF General Electric Keyboard and DisplayACT Menu TreeSET INFView Protection Settings Settings Group SET KEYView Settings Protection Modify Settings ProtectionConfirm Level Valid Range Setting OUT RangeStatus Information Group INF KEYSET DATE/TIME Control Group ACT KEYSingle KEY Menu Configuration Menu DBF Breaker Failure Protection GEK-106168E Figures Breaker Failure Logic 189C4114 Sheet External Connections 189C4114 Sheet Front View 226B7412 H9 Rear View 226B7412H10 Dimensions Diagram 226B6086H10 Panel Drilling 226B6086H10 RS232 Connection DBF Relay to PC