6. ACCEPTANCE TESTS

6.

ACCEPTANCE TESTS

 

 

6.1. CONNECTIONS AND NECESSARY EQUIPMENT

Necessary equipment:

One current source

One DC voltage source

Precision timer for testing timed events

One AC/DC voltmeter/ammeter

Connect the relay as indicated in the external connections diagram, Figure 2.

For safety reasons, the external protection earth should be securely grounded.

Apply dc rated voltage to terminals A10-B10

6.2. VISUAL INSPECTION

Check that the relay has not suffered any kind of damage due to transport and handling.

Check that all the screws are tight and the terminal blocks have not been damaged in any way.

6.3. PANEL INSULATION TESTS

!

If any insulation test would be performed on the panel where the relay is installed, the ground terminals A9-B9 must remain ungrounded.

Do the following groups in the terminals of the relay:

Group 1: A10, B10

Group 2: A1 to A4, B1 to B4

Group 3: C9, C10, D9, D10, C11, C12, D11, and D12

Group 4: A11, B11, A12, and B12

Group 5: C1, D1, C2, D2, C3, and D3

Group 6: C4, C5, C6, C7, C8, D4, D5, D6, D7, and D8

If the relay has expansion board, then the following groups must be added:

Group 7: E7, F7, E8, F8, E9, F9, E10, F10, E11, F11, E12, and F12

Group 8: E1, F1, E2, F2, E3, F3, E4, F4, E5, F5, E6, and F6

Apply 2000V gradually between case and groups.

Apply 2000V gradually between groups.

GEK-106168E

DBF Breaker Failure Protection

29

Image 36
Contents GE Power Management 3KRQHHVFULSWLRQ0DQXDO*RI.\RXUFRGHTXHVWLRQ Ruvxjjhvwlrqd Page Table of Contents Installation and Maintenance List of Figures Rear View 226B7412 SheetDBF Breaker Failure Protection GEK-106168E General Description Protection∙ Breaker internal arc detection Monitoring AnalysisDBF Breaker Failure Protection GEK-106168E Digital Signal Input # Terminals Protection FunctionsOvercurrent Units Low-Level Overcurrent Breaker Failure Unit 50BF 1PReset of Latching Relays Ground Overcurrent Breaker Failure UnitBreaker Failure without current or very low current Breaker Arc Detection DeviceInternal Protection Status Signals Monitoring and Recording FunctionsMeasurement Associated Breaker StatusGroup Status Comment Optional Exp. Board Optional Exp. Board Latched#1 ClosedOptional Exp.Boar Latched#2 Closed Internal Communication Status Signals LED Left Column Right Column Circuit Breaker Breaking Capacity MonitoringAnalysis Functions BUILT-IN SELF-CHECKING UnitEvent Recorder OscillographyEvents to Trigger Oscillography Tables of Settings ControlTable Selection Active Table INPUT-1 INPUT-0Configurable Inputs and Outputs Time SynchronizationFunction Outputs MAN-MACHINE Interface HMI Remote Communications Breaker Setting Group Active table setting groupCommon to all tables Range Default Step Oscillography Mask Independent for each table Range Default Step 50BF SettingsInternal Arc Settings Functions PermittedComments on Settings DBF Breaker Failure Protection GEK-106168E Ranges Models DBF Phase Model ListDBF GroundTechnical Characteristics MechanicalElectrical Communications StandardsTest Standard Class DBF Breaker Failure Protection GEK-106168E Physical Description CaseElectrical Connections Internal ConstructionDBF Breaker Failure Protection GEK-106168E Operating Theory Magnetic ModuleCPU Board Power Supply Keyboard and DisplayConnections and Necessary Equipment Visual InspectionPanel Insulation Tests Relay Setting IndicatorsPower Supply Communications Inputs Digital InputsIRIG-B Synchronizing Input Functions 1 50BF 1P Unit Test2 50BF 3P Unit Test Internal ARC Test 4 3P no I FunctionNeutral Overcurrent Unit Test DBF Breaker Failure Protection GEK-106168E Relay Measurement Tests Current MeasurementTiming Measurement DBF Breaker Failure Protection GEK-106168E Installation MaintenanceCONNECTION-TO-GROUND and Disturbances Suppression DBF Breaker Failure Protection GEK-106168E Keyboard and Display DBF General ElectricMenu Tree SETINF ACTSettings Group SET KEY View Settings ProtectionModify Settings Protection View Protection SettingsConfirm Setting OUT Range Level Valid RangeInformation Group INF KEY StatusControl Group ACT KEY SET DATE/TIMESingle KEY Menu Configuration Menu DBF Breaker Failure Protection GEK-106168E Figures Breaker Failure Logic 189C4114 Sheet External Connections 189C4114 Sheet Front View 226B7412 H9 Rear View 226B7412H10 Dimensions Diagram 226B6086H10 Panel Drilling 226B6086H10 RS232 Connection DBF Relay to PC