GE GEK 106168E manual Confirm

Page 51

8. KEYBOARD AND DISPLAY

Level 1

Level 2

Level 3

Level 4

 

FUNCTION

50BF 1P FUNCTION

 

PERM/NON-PERM.

 

50BF 3P FUNCTION

 

PERM/NON-PERM.

 

PERMIT

 

 

3P NO INT FUNCT.

 

PERM/NON-PERM.

 

 

 

 

 

PH HISET PICKUP

 

1.0-12A *

 

 

PH LOSET PICKUP

 

1.0-12A *

 

 

NEUTRAL PICKUP

 

0.5-6.0A *

 

 

1 PHASE TIMER T1

 

0.05-2s

 

 

3 PHASE TIMER T2

 

0.05-2s

 

50BF SETTINGS T1

3P NO I TIMER T3

 

0.05-2s

 

 

BF LOGIC (3P/2P)

 

3 PHASE/2 PHASE

 

 

SEVERE FAULT 3P

 

PERM./NON-PERM.

 

 

LOW LOAD 2P

 

PERM/NON-PERM

 

 

Nº OUTPUT STAGES

1 / 2

 

 

2nd STAGE TIMER

 

0.05-2s

 

50 BF SETTINGS T2

 

Same than for TABLE 1

 

50 BF SETTINGS T3

 

Same than for TABLE 1

 

INTERNAL ARC SET T1

INT ARC PICKUP

 

0.05-1A

 

 

INT ARC TIMER

 

0.1-2.0 s

 

INTERNAL ARC SET T2

 

Same than for TABLE 1

 

INTERNAL ARC SET T 3

 

Same than for TABLE 2

To change any setting the procedure is as follows:

Press the SET key.

Select the option MODIFY SETTINGS (using −↓ arrow keys).

Press ENT key.

Select the required setting group in the menu tree (with −↓ arrow keys).

Press ENT key.

Select the required specific setting (with −↓ arrow keys).

ENTER the value to be modified ( or select the required value from the list of available settings using right/left arrow keys).

Press the ENT key.

Press the END key.

The relay will request confirmation of the change by means of the following message:

CONFIRM

Y/N

To confirm the change, press the 1/Y key. (If not, press 3/N).

The relay will then show the following message on the screen (LCD):

SETTINGS CHANGE

EXECUTED

Press the CLR key four times to return to the main first screen (rest).

44

DBF Breaker Failure Protection

GEK-106168E

Image 51
Contents GE Power Management 3KRQHHVFULSWLRQ0DQXDO*RI.\RXUFRGHTXHVWLRQ Ruvxjjhvwlrqd Page Table of Contents Installation and Maintenance Rear View 226B7412 Sheet List of FiguresDBF Breaker Failure Protection GEK-106168E Analysis General DescriptionProtection ∙ Breaker internal arc detection MonitoringDBF Breaker Failure Protection GEK-106168E Low-Level Overcurrent Breaker Failure Unit 50BF 1P Digital Signal Input # TerminalsProtection Functions Overcurrent UnitsBreaker Arc Detection Device Reset of Latching RelaysGround Overcurrent Breaker Failure Unit Breaker Failure without current or very low currentAssociated Breaker Status Internal Protection Status SignalsMonitoring and Recording Functions MeasurementGroup Status Comment Optional Exp. Board Optional Exp. Board Latched#1 ClosedOptional Exp.Boar Latched#2 Closed Internal Communication Status Signals Circuit Breaker Breaking Capacity Monitoring LED Left Column Right ColumnOscillography Analysis FunctionsBUILT-IN SELF-CHECKING Unit Event RecorderEvents to Trigger Oscillography INPUT-1 INPUT-0 Tables of SettingsControl Table Selection Active TableConfigurable Inputs and Outputs Time SynchronizationFunction Outputs MAN-MACHINE Interface HMI Remote Communications Active table setting group Breaker Setting GroupFunctions Permitted Common to all tables Range Default Step Oscillography MaskIndependent for each table Range Default Step 50BF Settings Internal Arc SettingsComments on Settings DBF Breaker Failure Protection GEK-106168E Ground Ranges Models DBF PhaseModel List DBFTechnical Characteristics MechanicalElectrical Communications StandardsTest Standard Class DBF Breaker Failure Protection GEK-106168E Internal Construction Physical DescriptionCase Electrical ConnectionsDBF Breaker Failure Protection GEK-106168E Operating Theory Magnetic ModuleCPU Board Keyboard and Display Power SupplyConnections and Necessary Equipment Visual InspectionPanel Insulation Tests Relay Setting IndicatorsPower Supply Communications Inputs Digital InputsIRIG-B Synchronizing Input 1 50BF 1P Unit Test Functions2 50BF 3P Unit Test Internal ARC Test 4 3P no I FunctionNeutral Overcurrent Unit Test DBF Breaker Failure Protection GEK-106168E Relay Measurement Tests Current MeasurementTiming Measurement DBF Breaker Failure Protection GEK-106168E Installation MaintenanceCONNECTION-TO-GROUND and Disturbances Suppression DBF Breaker Failure Protection GEK-106168E DBF General Electric Keyboard and DisplayACT Menu TreeSET INFView Protection Settings Settings Group SET KEYView Settings Protection Modify Settings ProtectionConfirm Level Valid Range Setting OUT RangeStatus Information Group INF KEYSET DATE/TIME Control Group ACT KEYSingle KEY Menu Configuration Menu DBF Breaker Failure Protection GEK-106168E Figures Breaker Failure Logic 189C4114 Sheet External Connections 189C4114 Sheet Front View 226B7412 H9 Rear View 226B7412H10 Dimensions Diagram 226B6086H10 Panel Drilling 226B6086H10 RS232 Connection DBF Relay to PC