3. SETTINGS
3.SETTINGS
This section describes the settings of the DBF relay and the procedure to modify them. Table 3 shows the list of DBF settings, their range and resolution, and the factory default settings.
To view or to modify settings using the GE_LOCAL program connected to PORT 1, PORT 2 or PORT 3 the user has to perform the following steps:
∙Check that the available connection cable is in accordance with the diagram in Figure 7. Check correspondence between
∙Connect the cable between the relay (or modem) and the serial port of your computer.
∙Run the
∙Make sure that the communication parameters in GE_LOCAL match with those set on the DBF. Specifically, the parameters on the configuration of the local HMI are:
∗COMMUNICATION SPEED: On the relay depending on whether communication is: through PORT 1 or PORT 2 (means LOCAL), or PORT 3 (means NET)
∗STOP BIT:
NET
To modify or view the DBF communication parameters refer to Chapter 8, Section 8.1 “Menu Tree”.
IMPORTANT: It should be noted that in order to simplify the setting of the unit and for safety reasons, all settings related with the configuration of the unit (configurable inputs and outputs, internal status events and target LED’s) have been removed from the HMI facilities and also from the communications software GE_LOCAL. To perform these configurations the GE_INTRO software (described in instruction book
TABLE 3. Settings Table
Common to all tables | Range | Default | Step |
| General Settings Group |
|
|
Relay status | In/out of service |
| |
Identification | 20 ASCII characters | No ID |
|
Frequency | 50 / 60 Hz | 50 Hz |
|
Phase CT Ratio | 1 | 1 | |
Neutral CT Ratio | 1 | 1 |
Breaker Setting Group
Breaker Number | 4 ASCII characters |
| 0000 |
|
kI2t Operation Mode |
| Fixed |
| |
Integration Time for kI2t |
| 0.06s | 0.01s | |
kI2t Maximum Limit |
| 99999 | 1 | |
|
|
|
| |
| Active table setting group |
|
| |
Active setting table # | 1 - 3 |
| 1 | 1 |
DBF Breaker Failure Protection | 17 |