GE GEK 106168E manual Relay Setting, Indicators, Power Supply

Page 37

6. ACCEPTANCE TESTS

6.4. RELAY SETTING

Introduce the following settings in the relay (by means of HMI or GE_Local software):

General Settings Group

Value

Relay Status

IN SERV

Identification

N/A

Frequency

50 Hz / 60 Hz

Phase CT Ratio

1

Neutral CT Ratio

1

Breaker Settings

Value

Breaker Number

N/A

KI2t Op. Mode

Fixed

KI2t INT. Time

0.06s

KI2t LIMIT

99999

Active Table Set

Value

Active Table

1

Function Permit

Value

50BF 1P Function

No Per

50BF 3P Function

No Per

3P NO INT Funct

No Per

50BF Settings Table 1

Value

PH Hiset Pickup

2A

PH Loset Pickup

1A

Neutral Pickup

1A

1 Phase Timer T1

1s

3 Phase Timer T2

1s

3P No I Timer T3

2s

BF Logic (3p/2P)

2 PHASE

Severe Fault 3P

Per

Low Load 2P

No Per

Nº Output Stages

1

2nd Stage Timer

2s

Internal Arc Settings Table 1

Value

Int Arc Pickup

1A

Int Arc Timer

1s

The specific settings required for each test are indicated; other settings do not affect the tests.

6.5. INDICATORS

Check that pressing the TARGET RESET button (with relay fed with rated dc power supply) all target LEDs light up.

6.6. POWER SUPPLY

The relay operates with a dc power supply within ± 20% of the rated value. Check that the READY target LED in the front of the relay lights up showing green color.

1.Apply dc rated voltage to terminals A10-B10

2.Change setpoint FUNCTION PERMIT/50BF 1P FUNCTION to PERM.

3.Apply 2A to terminals A1-A2.

4.Energize digital input CC1 PHASE A BF INITIATE (C9-D10).

5.Wait 1second.

6.Check that the READY target LED in the front of the relay lights up showing green color.

7.Check the dc burden (see table below)

30

DBF Breaker Failure Protection

GEK-106168E

Image 37
Contents GE Power Management 3KRQHHVFULSWLRQ0DQXDO*RI.\RXUFRGHTXHVWLRQ Ruvxjjhvwlrqd Page Table of Contents Installation and Maintenance Rear View 226B7412 Sheet List of FiguresDBF Breaker Failure Protection GEK-106168E Protection General Description∙ Breaker internal arc detection Monitoring AnalysisDBF Breaker Failure Protection GEK-106168E Protection Functions Digital Signal Input # TerminalsOvercurrent Units Low-Level Overcurrent Breaker Failure Unit 50BF 1PGround Overcurrent Breaker Failure Unit Reset of Latching RelaysBreaker Failure without current or very low current Breaker Arc Detection DeviceMonitoring and Recording Functions Internal Protection Status SignalsMeasurement Associated Breaker StatusGroup Status Comment Optional Exp. Board Closed Optional Exp. Board Latched#1Optional Exp.Boar Latched#2 Closed Internal Communication Status Signals Circuit Breaker Breaking Capacity Monitoring LED Left Column Right ColumnBUILT-IN SELF-CHECKING Unit Analysis FunctionsEvent Recorder OscillographyEvents to Trigger Oscillography Control Tables of SettingsTable Selection Active Table INPUT-1 INPUT-0Time Synchronization Configurable Inputs and OutputsFunction Outputs MAN-MACHINE Interface HMI Remote Communications Active table setting group Breaker Setting GroupIndependent for each table Range Default Step 50BF Settings Common to all tables Range Default Step Oscillography MaskInternal Arc Settings Functions PermittedComments on Settings DBF Breaker Failure Protection GEK-106168E Model List Ranges Models DBF PhaseDBF GroundMechanical Technical CharacteristicsElectrical Standards CommunicationsTest Standard Class DBF Breaker Failure Protection GEK-106168E Case Physical DescriptionElectrical Connections Internal ConstructionDBF Breaker Failure Protection GEK-106168E Magnetic Module Operating TheoryCPU Board Keyboard and Display Power SupplyVisual Inspection Connections and Necessary EquipmentPanel Insulation Tests Indicators Relay SettingPower Supply Communications Digital Inputs InputsIRIG-B Synchronizing Input 1 50BF 1P Unit Test Functions2 50BF 3P Unit Test 4 3P no I Function Internal ARC TestNeutral Overcurrent Unit Test DBF Breaker Failure Protection GEK-106168E Current Measurement Relay Measurement TestsTiming Measurement DBF Breaker Failure Protection GEK-106168E Maintenance InstallationCONNECTION-TO-GROUND and Disturbances Suppression DBF Breaker Failure Protection GEK-106168E DBF General Electric Keyboard and DisplaySET Menu TreeINF ACTView Settings Protection Settings Group SET KEYModify Settings Protection View Protection SettingsConfirm Level Valid Range Setting OUT RangeStatus Information Group INF KEYSET DATE/TIME Control Group ACT KEYSingle KEY Menu Configuration Menu DBF Breaker Failure Protection GEK-106168E Figures Breaker Failure Logic 189C4114 Sheet External Connections 189C4114 Sheet Front View 226B7412 H9 Rear View 226B7412H10 Dimensions Diagram 226B6086H10 Panel Drilling 226B6086H10 RS232 Connection DBF Relay to PC