GE GEK 106168E Analysis Functions, BUILT-IN SELF-CHECKING Unit, Event Recorder, Oscillography

Page 17

2. OPERATION LOGIC

2.2.5 BUILT-IN SELF-CHECKING UNIT

The digital technology of the DBF system allows providing a built-in self-checking function which guarantees the correct performance of the unit, and provides an external alarm in case of error detection.

Two built-in self-checking functions are performed, one when the unit is started up and the other during normal operation. Internal tests are provided for power supply, program memory (ROM), working memory (RAM), oscillography memory (RAM), and settings and calibration memory (EEPROM).

In addition, there is a hardware test for the Target LEDs, which lights them all up when the button TARGET RESET is pressed. The sealed-in targets (latched) reset if the TARGET RESET button is kept pressed during three seconds.

2.3. ANALYSIS FUNCTIONS.

The DBF system includes an event recorder and an oscillography waveform recorder with a resolution of 1 ms for the first one, and 1 sample for the second one (1.04 ms at 60 Hz and 1.25 ms at 50 Hz). To avoid the loss of date/time and oscillography records during any Vdc power failure, the unit is equipped with a capacitor, which allows the information to be kept for at least 24 hours after power loss.

2.3.1 EVENT RECORDER.

The DBF system keeps a record of the last 144 events and stores for each one the following information: date and time (accurate to one millisecond), the type of event, current RMS values during the event, and the state of the unit (set of digital signals that describes the status of the relay at any given moment in time).

This event recorder is stored in a non-volatile memory and can be maintained indefinitely, even with no power supply.

The list of events that the relay stores are factory fixed, and corresponds to standard relevant situations/operations, like Settings Change, Program initiate, Active Table 1, Opening 52 phase C, Closing 52 phase C, Digital Input 1 Activated, etc.

2.3.1 OSCILLOGRAPHY

The DBF unit stores up to 4 oscillography records, with a resolution of 16 samples per cycle. Each record has a maximum capacity of 66 cycles. The number of pre-fault cycles can be selected from 2 to 10 cycles. Each record includes the following information:

Date and time.

Name of the signal that triggered the oscillography.

Active settings table when recording

Digital information (Status of internal digital signals)

Instantaneous rms values of currents (IA, IB, IC and IN)

A configurable mask is available for selecting which functions or internal signals are able to trigger the oscillography. It can either be triggered by a configurable digital input, by a command received from the communication program (GE_LOCAL), or directly from the HMI.

10

DBF Breaker Failure Protection

GEK-106168E

Image 17
Contents GE Power Management 3KRQHHVFULSWLRQ0DQXDO*RI.\RXUFRGHTXHVWLRQ Ruvxjjhvwlrqd Page Table of Contents Installation and Maintenance Rear View 226B7412 Sheet List of FiguresDBF Breaker Failure Protection GEK-106168E Protection General Description∙ Breaker internal arc detection Monitoring AnalysisDBF Breaker Failure Protection GEK-106168E Protection Functions Digital Signal Input # TerminalsOvercurrent Units Low-Level Overcurrent Breaker Failure Unit 50BF 1PGround Overcurrent Breaker Failure Unit Reset of Latching RelaysBreaker Failure without current or very low current Breaker Arc Detection DeviceMonitoring and Recording Functions Internal Protection Status SignalsMeasurement Associated Breaker StatusGroup Status Comment Optional Exp. Board Optional Exp.Boar Latched#2 Closed Optional Exp. Board Latched#1Closed Internal Communication Status Signals Circuit Breaker Breaking Capacity Monitoring LED Left Column Right ColumnBUILT-IN SELF-CHECKING Unit Analysis FunctionsEvent Recorder OscillographyEvents to Trigger Oscillography Control Tables of SettingsTable Selection Active Table INPUT-1 INPUT-0Function Configurable Inputs and OutputsTime Synchronization Outputs MAN-MACHINE Interface HMI Remote Communications Active table setting group Breaker Setting GroupIndependent for each table Range Default Step 50BF Settings Common to all tables Range Default Step Oscillography MaskInternal Arc Settings Functions PermittedComments on Settings DBF Breaker Failure Protection GEK-106168E Model List Ranges Models DBF PhaseDBF GroundElectrical Technical CharacteristicsMechanical Test Standard Class CommunicationsStandards DBF Breaker Failure Protection GEK-106168E Case Physical DescriptionElectrical Connections Internal ConstructionDBF Breaker Failure Protection GEK-106168E CPU Board Operating TheoryMagnetic Module Keyboard and Display Power SupplyPanel Insulation Tests Connections and Necessary EquipmentVisual Inspection Power Supply Relay SettingIndicators Communications IRIG-B Synchronizing Input InputsDigital Inputs 1 50BF 1P Unit Test Functions2 50BF 3P Unit Test Neutral Overcurrent Unit Test Internal ARC Test4 3P no I Function DBF Breaker Failure Protection GEK-106168E Timing Measurement Relay Measurement TestsCurrent Measurement DBF Breaker Failure Protection GEK-106168E CONNECTION-TO-GROUND and Disturbances Suppression InstallationMaintenance DBF Breaker Failure Protection GEK-106168E DBF General Electric Keyboard and DisplaySET Menu TreeINF ACTView Settings Protection Settings Group SET KEYModify Settings Protection View Protection SettingsConfirm Level Valid Range Setting OUT RangeStatus Information Group INF KEYSET DATE/TIME Control Group ACT KEYSingle KEY Menu Configuration Menu DBF Breaker Failure Protection GEK-106168E Figures Breaker Failure Logic 189C4114 Sheet External Connections 189C4114 Sheet Front View 226B7412 H9 Rear View 226B7412H10 Dimensions Diagram 226B6086H10 Panel Drilling 226B6086H10 RS232 Connection DBF Relay to PC