B&B Electronics I-7011 user manual 37 ~AA4, Syntax ~AA4CHKcr, AAPPSSCHKcr

Page 59

2.37 ~AA4

Description : Read PowerOn Value and Safe Value

Syntax : ~AA4[CHK](cr)

~delimiter character

AA

address of reading module (00 to FF)

4

command for reading PowerOn Value and Safe Value

Response : Valid Command :

!AAPPSS[CHK](cr)

 

Invalid Command :

?AA[CHK](cr)

 

Syntax error or communication error may get no re-

 

sponse.

 

!

delimiter for valid command

 

?delimiter for invalid command

AA address of response module(00 to FF)

PPPowerOn Value, 00=DO0 off,DO1 off, 01=DO0 on,DO1 off, 02=DO0 off, DO1 on, 03=DO0 on, DO1 on

SSSafe Value, data format is same as PP Example :

Command : ~014Receive : !010000

Read address 01 PowerOn/Safe Value, return PowerOn Value is DO0 off, DO1 off, Safe Value is DO0 off, DO1 off.

Related Command :

Sec.2.38 ~AA5PPSS

Related Topic :

Sec.3.2 Module Status, Sec.3.3 Dual Watchdog Operation Note : The command is for I-7011/11D/11P/11PD only

Rev:B1.0

I-7011, I-7018 User Manual

59

Image 59
Contents Trademark WarrantyCopyright Table of Contents @AADOData High/Low Alarm More Information IntroductionPin Assignment RevB1.0 7011/I-7011D Specifications7011P/I-7011PD 7018P 7018Block Diagram Wire Connection Page Quick Start Default SettingJumper Setting Don’t Perform Calibrate Until You Really Understand CalibrationData Format Setting FF Configuration TablesBaudrate Setting CC Analog Input Type Setting TT Type Input Range Data Format +F.S Zero Code Analog input type and data format tableRevB1.0 Type Input Range Data Format +F.S Zero Code Command Sec.2.19 ?AACHKcr Related CommandSyntax %AANNTTCCFFCHKcr AACHKcrExample Syntax #**CHKcrSyntax #AACHKcr #AASyntax #AANCHKcr Response Valid Command DataCHKcr Invalid Command ?AACHKcr#AAN Syntax $AA0CHKcr $AA0Syntax $AA1CHKcr $AA1FF data format of module reference Sec.1.10 Example $AA2Syntax $AA2CHKcr AATTCCFFCHKcrSyntax $AA3CHKcr $AA3Data synchronized data, format reference Sec.1.10 Example $AA4Syntax $AA4CHKcr AASDataCHKcrSyntax $AA5VVCHKcr 10 $AA5VVAAVVCHKcr 11 $AA6Syntax $AA6CHKcr AAVCHKcr 12 $AA8Syntax $AA8CHKcr Syntax $AA8VCHKcr 13 $AA8VAA address of response module 00 to FF Example Related Command Sec.2.8 $AA314 $AA9Data Syntax $AA9DataCHKcrAASCHKcr 15 $AABSyntax $AABCHKcr AADataCHKcr 16 $AAFSyntax $AAFCHKcr Syntax $AAMCHKcr 17 $AAMSyntax $AAZDataCHKcr 18 $AAZDataSyntax ~AAODataCHKcr Read address 01 module name, return 7018. Related Command19 ~AAOData Related Topic 20 ~AAEVSyntax ~AAEVCHKcr Level. Example 21 @AADISyntax @AADICHKcr AASOOIICHKcrHigh 22 @AADOData Syntax @AAEATCHKcr 23 @AAEAT24 @AAHIData 25 @AALOData Syntax @AADACHKcr Related Command Sec.2.23 @AAEAT Related Topic26 @AADA Syntax @AACACHKcr 27 @AACASyntax @AARHCHKcr Read address 01 high alarm, return +2.5000. Related Command28 @AARH 29 @AARL Syntax @AARECHKcr Read address 01 event counter, return 1234. Related Command30 @AARE Syntax @AACECHKcr 31 @AACEResponse No response. Example 32 ~Description Host OK Syntax ~**CHKcrAASSCHKcr Host watchdog timeout flag, 0=Clear, 1=Set Example33 ~AA0 Syntax ~AA0CHKcr Syntax ~AA1CHKcr 34 ~AA1Syntax ~AA2CHKcr 35 ~AA2Syntax ~AA3EVVCHKcr 36 ~AA3EVVSS Safe Value, data format is same as PP Example 37 ~AA4Syntax ~AA4CHKcr AAPPSSCHKcrSyntax ~AA5PPSSCHKcr 38 ~AA5PPSSModule Status INIT* pin OperationDual Watchdog = Module Watchdog + Host Watchdog Dual Watchdog OperationDigital Input and Event Counter Digital OutputThermocouple Measurement High/Low Alarm