B&B Electronics I-7011 user manual Syntax $AA3CHKcr

Page 29

2.8 $AA3

Description : Read CJC Temperature

Syntax : $AA3[CHK](cr)

$

delimiter character

 

AA

address of reading module (00 to FF)

3

command for reading CJC temperature

Response : Valid Command :

>(Data)[CHK](cr)

 

Invalid Command :

?AA[CHK](cr)

Syntax error or communication error may get no re- sponse.

>delimiter for valid command

? delimiter for invalid command

AA address of response module(00 to FF)

(Data) CJC temperature in degree Celsius.

Example :

Command : $033Receive : >+0025.4

Read address 03 CJC temperature, return 25.4°C.

Related Command :

Sec.2.14 $AA9(Data)

Rev:B1.0

I-7011, I-7018 User Manual

29

Image 29
Contents Trademark WarrantyCopyright Table of Contents @AADOData High/Low Alarm More Information IntroductionPin Assignment RevB1.0 7011/I-7011D Specifications7011P/I-7011PD 7018P 7018Block Diagram Wire Connection Page Quick Start Default SettingJumper Setting Don’t Perform Calibrate Until You Really Understand CalibrationData Format Setting FF Configuration TablesBaudrate Setting CC Analog Input Type Setting TT Type Input Range Data Format +F.S Zero Code Analog input type and data format tableRevB1.0 Type Input Range Data Format +F.S Zero Code Command Sec.2.19 Syntax %AANNTTCCFFCHKcr Related CommandAACHKcr ?AACHKcrExample Syntax #**CHKcrSyntax #AACHKcr #AASyntax #AANCHKcr Response Valid Command DataCHKcr Invalid Command ?AACHKcr#AAN Syntax $AA0CHKcr $AA0Syntax $AA1CHKcr $AA1Syntax $AA2CHKcr $AA2AATTCCFFCHKcr FF data format of module reference Sec.1.10 ExampleSyntax $AA3CHKcr $AA3Syntax $AA4CHKcr $AA4AASDataCHKcr Data synchronized data, format reference Sec.1.10 ExampleSyntax $AA5VVCHKcr 10 $AA5VVAAVVCHKcr 11 $AA6Syntax $AA6CHKcr AAVCHKcr 12 $AA8Syntax $AA8CHKcr Syntax $AA8VCHKcr 13 $AA8V14 $AA9Data Related Command Sec.2.8 $AA3Syntax $AA9DataCHKcr AA address of response module 00 to FF ExampleAASCHKcr 15 $AABSyntax $AABCHKcr AADataCHKcr 16 $AAFSyntax $AAFCHKcr Syntax $AAMCHKcr 17 $AAMSyntax $AAZDataCHKcr 18 $AAZDataSyntax ~AAODataCHKcr Read address 01 module name, return 7018. Related Command19 ~AAOData Related Topic 20 ~AAEVSyntax ~AAEVCHKcr Syntax @AADICHKcr 21 @AADIAASOOIICHKcr Level. ExampleHigh 22 @AADOData Syntax @AAEATCHKcr 23 @AAEAT24 @AAHIData 25 @AALOData Syntax @AADACHKcr Related Command Sec.2.23 @AAEAT Related Topic26 @AADA Syntax @AACACHKcr 27 @AACASyntax @AARHCHKcr Read address 01 high alarm, return +2.5000. Related Command28 @AARH 29 @AARL Syntax @AARECHKcr Read address 01 event counter, return 1234. Related Command30 @AARE Syntax @AACECHKcr 31 @AACEDescription Host OK 32 ~Syntax ~**CHKcr Response No response. Example33 ~AA0 Host watchdog timeout flag, 0=Clear, 1=Set ExampleSyntax ~AA0CHKcr AASSCHKcrSyntax ~AA1CHKcr 34 ~AA1Syntax ~AA2CHKcr 35 ~AA2Syntax ~AA3EVVCHKcr 36 ~AA3EVVSyntax ~AA4CHKcr 37 ~AA4AAPPSSCHKcr SS Safe Value, data format is same as PP ExampleSyntax ~AA5PPSSCHKcr 38 ~AA5PPSSModule Status INIT* pin OperationDigital Input and Event Counter Dual Watchdog OperationDigital Output Dual Watchdog = Module Watchdog + Host WatchdogThermocouple Measurement High/Low Alarm