B&B Electronics I-7011 Calibration, Don’t Perform Calibrate Until You Really Understand

Page 15

1.9 Calibration

Don’t Perform Calibrate Until You Really Understand.

Calibration Requirement for I-7011/11D/11P/11PD/18/18P

Type Code

00

01

02

03

04

05

06

 

 

 

 

 

 

 

 

Min. Input

0 mV

0 mV

0 mV

0 mV

0 V

0 V

0 mA

 

 

 

 

 

 

 

 

Max Input

+15

+50

+100

+500

+1 V

+2.5 V

+20

mV

mV

mV

mV

mA

 

 

 

 

 

 

 

 

 

 

 

Notification :

1While calibrate type 06, need connect external shunt resistor, 125 ohms, 0.1% (Ref Sec.1.5).

2Connect calibration voltage(or current) signal to module’s input. For I-7018/18P, connect to channel 0. (Wire connect ref Sec.1.5)

3Before calibration, warm-up module about 30 minutes for bet- ter accuracy.

Example Calibration Sequence for Type 00 :

 

 

1

Setting Type to 00

->

Ref

 

Sec.2.1.

 

 

2

Enable Calibration

->

Ref

 

Sec.2.20.

 

 

3

Apply Zero Calibration Voltage (0mV)

 

 

4

Preform Zero Calibration Command

-> Ref Sec.2.6.

5

Apply Span Calibration Voltage (15mV)

 

 

6

Perform Span Calibration Command

-> Ref Sec.2.5.

7

Repeat step1 to step6 three times.

 

 

Calibration sequence for other type is similiar but different in step

1 to set different type.

15

Rev:B1.0

I-7011, I-7018 User Manual

Image 15
Contents Warranty CopyrightTrademark Table of Contents @AADOData High/Low Alarm More Information IntroductionPin Assignment RevB1.0 7011/I-7011D Specifications7011P/I-7011PD 7018P 7018Block Diagram Wire Connection Page Default Setting Jumper SettingQuick Start Don’t Perform Calibrate Until You Really Understand CalibrationConfiguration Tables Baudrate Setting CC Analog Input Type Setting TTData Format Setting FF Type Input Range Data Format +F.S Zero Code Analog input type and data format tableRevB1.0 Type Input Range Data Format +F.S Zero Code Command Sec.2.19 ?AACHKcr Related CommandSyntax %AANNTTCCFFCHKcr AACHKcrExample Syntax #**CHKcrSyntax #AACHKcr #AAResponse Valid Command DataCHKcr Invalid Command ?AACHKcr #AANSyntax #AANCHKcr Syntax $AA0CHKcr $AA0Syntax $AA1CHKcr $AA1FF data format of module reference Sec.1.10 Example $AA2Syntax $AA2CHKcr AATTCCFFCHKcrSyntax $AA3CHKcr $AA3Data synchronized data, format reference Sec.1.10 Example $AA4Syntax $AA4CHKcr AASDataCHKcrSyntax $AA5VVCHKcr 10 $AA5VV11 $AA6 Syntax $AA6CHKcrAAVVCHKcr 12 $AA8 Syntax $AA8CHKcrAAVCHKcr Syntax $AA8VCHKcr 13 $AA8VAA address of response module 00 to FF Example Related Command Sec.2.8 $AA314 $AA9Data Syntax $AA9DataCHKcr15 $AAB Syntax $AABCHKcrAASCHKcr 16 $AAF Syntax $AAFCHKcrAADataCHKcr Syntax $AAMCHKcr 17 $AAMSyntax $AAZDataCHKcr 18 $AAZDataRead address 01 module name, return 7018. Related Command 19 ~AAODataSyntax ~AAODataCHKcr 20 ~AAEV Syntax ~AAEVCHKcrRelated Topic Level. Example 21 @AADISyntax @AADICHKcr AASOOIICHKcrHigh 22 @AADOData Syntax @AAEATCHKcr 23 @AAEAT24 @AAHIData 25 @AALOData Related Command Sec.2.23 @AAEAT Related Topic 26 @AADASyntax @AADACHKcr Syntax @AACACHKcr 27 @AACARead address 01 high alarm, return +2.5000. Related Command 28 @AARHSyntax @AARHCHKcr 29 @AARL Read address 01 event counter, return 1234. Related Command 30 @AARESyntax @AARECHKcr Syntax @AACECHKcr 31 @AACEResponse No response. Example 32 ~Description Host OK Syntax ~**CHKcrAASSCHKcr Host watchdog timeout flag, 0=Clear, 1=Set Example33 ~AA0 Syntax ~AA0CHKcrSyntax ~AA1CHKcr 34 ~AA1Syntax ~AA2CHKcr 35 ~AA2Syntax ~AA3EVVCHKcr 36 ~AA3EVVSS Safe Value, data format is same as PP Example 37 ~AA4Syntax ~AA4CHKcr AAPPSSCHKcrSyntax ~AA5PPSSCHKcr 38 ~AA5PPSSModule Status INIT* pin OperationDual Watchdog = Module Watchdog + Host Watchdog Dual Watchdog OperationDigital Input and Event Counter Digital OutputThermocouple Measurement High/Low Alarm