NCR 7882 manual Ventilation Requirements, Electrical Wiring

Page 35

NCR RealScan 7882 Installation and Owner Guide

Ventilation Requirements

The RealScan 7882 Scanner/Scale is designed to operate without an exhaust fan in the checkstand; however, there must be adequate convection air flow. The ambient temperature inside the checkstand cannot be higher than 104° F (40° C). Also, the ambient temperature inside the checkstand cannot be higher than 12.6° F (7° C) above the ambient temperature outside the checkstand. For example, if the ambient temperature outside the checkstand is 76° F (24.4° C), the ambient temperature inside the checkstand cannot be greater than 88.6° F (31.4° C). If the checkstand contains other heat producing equipment, you may need to use forced air to keep the temperature within the specified range. However, air coming into or leaving the checkstand MUST NOT enter or exit past the RealScan 7882 Scanner/Scale.

Electrical Wiring

Input

Voltage

Neutral and Ground Bus

L3

Main Service

Panel

 

Belt Control

Belt

N

Lighting

Motor

Misc. Equip.

G

 

Conduit

Circuit A: Checkstand

Checkstand

Frame

Note: The electrical wiring must meet all electrical codes, laws, and regulations.

Feeder wiring and insulated ground from main service panel to distribution panel to be run in metal conduit.

Isolated/Insulated

Circuit Breakers

 

Ground Bus

NCR circuits should be run in

 

separate metal Conduits.

 

Note: NCR circuits must be dedicated to

L1

NCR equipment or other logically

connected electronic equipment

 

 

(modems, DAA, bridges, etc.)

 

Circuit B: Terminal

L2

 

Neutral

Circuit C: Scanner

Receptacle should be easily

Bus

accessible and near the scanner

Distribution Panel

 

 

Isolated Ground Receptacles

Installation Type

Input Voltage

L1, L2

Circuit Breakers

 

 

 

 

U.S., Canada, &

100Vac to 120Vac

100Vac to 120Vac

Standard single-pole; value

Japan

 

 

determined by type of device

 

 

 

International

220Vac to 240Vac

220Vac to 240Vac

branch and by electrical code.

 

 

 

 

European

220Vac

220Vac

European double-pole.

20254

497-0419630 Release F

09/02

35 of 62

Image 35
Contents RealScan Installation and Owner Guide Revision Record ContentsObtaining Technical Assistance Obtaining Additional InformationRealScan RealScan 7882 MountingsStep Installation InstructionsConnecting the Cables to an NCR RealScan Installing Power Supply Interface CablesUSB Interface Connection IBM HID Auxiliary RS-232 Port Auxiliary RS-232 PortProgramming the Communication Parameters Setting Program Parameters and Verifying Host ConnectionTurning on the RealScan RS-232 NCR 2170, 7452 Ocia Short Format NCR 2113, 2126 RS-232 Ruby Verifone Ruby 4M UPC/EAN Programming DefaultsPrefix Byte Disable Ascii Code RS-232 Communications Programming for USB ConnectionMaking Other Program Changes UPC-A Scan Sample Tags1234 5 678 Determining Label QualityScan Zone Adjusting Screw Setting RealScan Scan ZoneVertical Pass-by Scanning Horizontal Pass-by ScanningVertical Presentation Scanning from Bottom Vertical Presentation Scanning from TopPlastic Top Plate Mounting RealScanRubber Feet Connect Power Cable and Interface Cable Vertical Mounting Bracket Cable Clamps Checkstand CutoutCheckpoint Cable Operating the Scanner Cleaning the Scanner Green Status Indicator Tones Problem Suspect Component Correcting Scanner ProblemsNCR RealScan 7882 Installation and Owner Guide Most Common Interface Cables Interface ConnectorInterface Information Protocol Communications ProtocolProgramming Worksheet Checkstand Hole RealScan 7882 Horizontal Mount NCR RealScan SpecificationsCheckstand Hole RealScan 7882 Flat Mount Ventilation Requirements Electrical WiringTone On/Off Programming WorksheetsPeriodical Codes Version DExtend UPC-A To EAN-13 Extend UPC-E To UPC-ATransmit Check Digit CodeMinimum Characters Allowed Full Ascii Check Digit PresentBar Code Type Minimum Data Characters Allowed UCCIdentifier Type Common ByteHandshake Baud RateParity Stop Bits Character LengthIBM Tone Control Good Read Tone Control Message DelayNormal or Eavesdrop Mode Terminator ByteAscii Code Chart Regulatory Information CE Mark Applicability Identification LabelsDeclaration of Conformity Laser Safety Label Laser SafetyLaser Module Label Laser PowerProgramming Tags Volume Adjustment ResetDefault Programming Mode End Save and Reset Abort Diagnostic Mode RS-232 Temporary Service Mode Mode Reset Tallies Hex Hex Hex Hex Hex Hex a Hex B Hex C Hex D Hex E Hex F Copyright 2001, 2002 by NCR Corporation