FieldServer FS-8700-80 instruction manual DACHILLER1

Page 10

McQuay Micro Tech Open Protocol Driver Manual

Page 10 of 35

4.4.4.Map Descriptor Example 1 – Read Everything.

In this example the Map Descriptor tells the driver to read all data fields known for the Node. The data fields are read sequentially and the value obtained placed in the Data Array at a location determined by the driver. Appendix A.2 outlines the data read and the Data Array location of each field. There is no way of telling this command to read some fields more often than others. Each field is read in turn and when the end of the list is reached the driver starts at the beginning again.

Map_Descriptor_Name

,Data_Array_Name

,Data_Array_Offset

,Function

,Node_Name

,Length

,Scan_Interval

,Field_Name

,Device_Scaling

Read Chiller 1

,DA_CHILLER1

,0

,Rdbc

,Chiller1

,1

,1.0s

,Everything

,Yes

 

 

 

 

 

 

 

 

 

This parameter does not affect the functionality of the driver, however, many validation or error messages report the name of the Map Descriptor in the message and, thus it is strongly recommended that unique names be used.

Each field read has its value stored in this Data Array. The location is dependent on the field name. Ensure that the length of the Data Array is at least 200, so that all parameters can be stored.

 

 

The values will be

 

 

scaled before

This parameter

The driver will

storage.

 

connects the Map

read every data

Example: The

Descriptor to a

field known for the

‘Evaporator

node which in turn

device.

Refrigerant

connects the Map

 

 

Pressure’ will be

Descriptor to a

 

 

stored by dividing

port.

 

 

the raw value read

 

 

 

 

by 10.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldServer.com

Image 10
Contents Driver Manual FS-8700-80 McQuay Micro Tech Open Protocol Table of Contents Page McQuay Micro Tech Open Protocol Driver Manual Hardware Connections Provided by Supplier of 3rd Party EquipmentFieldServer Data Arrays Page Page Driver Related Map Descriptor Parameters Timing ParametersDACHILLER1 Map Descriptor Example 3 Write DamodesPage Page Driver Specific Map Descriptor Parameters DACHILLER1 Passive Chiller1 1024 256 Chiller1emulation2 Page Equipment Type 200CFC 200 Series Centrifugal Chiller McQuay Micro Tech Open Protocol Driver Manual Equipment Type 050RPC Reciprocating Chiller McQuay Micro Tech Open Protocol Driver Manual Page McQuay Micro Tech Open Protocol Driver Manual Equipment Type 001ASC Reciprocating Chiller Equipment Type Self-Contained Units SCUs McQuay Micro Tech Open Protocol Driver Manual Appendix A.3 McQuay Equipment Types recognized by the driver Appendix A.4. Direct AddressingPage DACHILLER1 DACHILLER1 NAK Damcqstats UINT32 Page McQuay Micro Tech Open Protocol Driver Manual Appendix C.3. Node ID problems Appendix C.2. Negative Acknowledgement NAK