McQuay Micro Tech Open Protocol Driver Manual | Page 4 of 35 |
PC Connection
The PC connection to a MicroTech controller is through an available port A that is configured as TTY. It is best to connect the PC to a
You can connect two or more PCs to the network, but only one PC can be connected to a particular controller. The PC that you use most often should be connected to the
If a PC is connected to a
Port Configuration: The communications port that the PC is connected to must be configured as a TTY port. The default port configuration for most MicroTech controllers sets port A as TTY. The port configuration is a software setting.
A separate software setting defines the communications rate of each port. In most controllers, the default rate is 9600 bps.
TTY: A TTY port is used to connect a PC for monitoring purposes. It uses the
5.The following quote from “MicroTech® Data Terminal Communication Packets, Open Protocol™ Data Communications Information Packet ” highlights an important limitation of the protocol.
Data terminal communications may be sent via
6.Each MicroTech controller is shipped from the factory with a unique job site password. The passwords are provided by the McQuay International representative at the time of startup.
7.The driver does not validate passwords when configured as a Server. This means that requests to read or write data will succeed even if the password supplied with the request is incorrect.