FieldServer FS-8700-80 instruction manual

Page 22

McQuay Micro Tech Open Protocol Driver Manual

 

Page 22 of 35

Table 4 - Equipment Type: 100CFC 100 Series Centrifugal Chiller

 

 

 

 

Array

Read/

 

Number

Base

Device

 

 

Write/

Field Name

Scaling7

 

 

Location

of Bytes

Address

 

 

 

 

 

 

Both

 

 

 

Method

 

 

1

r

Alarm Contact

1

0x0217

1

 

 

2

r

Approach Condenser

1

0x0418

1

 

 

3

r

Calculated Leaving Evaporator Temp Setpoint

1

0x0420

7

 

 

4

r

Calculated Network Amp Limit Setpoint

1

0x0423

1

 

 

5

r

Compressor Discharge Temp.

1

0x0407

1

 

 

6

r

Compressor Suction Temp. - Lo Resolution

1

0x0403

1

 

 

7

r

Compressor Suction Temp. - Hi Resolution

1

0x041C

7

 

 

8

r

Condenser Pump

1

0X021C

1

 

 

9

r

Condenser Refrigerant Pressure

1

0x0411

1

 

 

10

r

Condenser Refrigerant Temp.

1

0x0408

1

 

 

11

r

Condenser Water Flow Switch

1

0X050F

1

 

 

12

r

Cooling Tower Stage 1

1

0x0218

1

 

 

13

r

Cooling Tower Stage 2

1

0x0219

1

 

 

14

r

Current Fault

1

0x0428

1

 

 

15

r

Fault Last

1

0x0834

1

 

 

16

r

Fault 2

1

0x0835

1

 

 

17

r

Fault 3

1

0x0836

1

 

 

18

r

Fault 4

1

0x0837

1

 

 

19

r

Fault 5

1

0x0838

1

 

 

20

r

Fault 6

1

0x0839

1

 

 

21

r

Fault 7

1

0x083A

1

 

 

22

r

Fault 8

1

0x083B

1

 

 

23

r

Entering Condenser Water Temp. - Lo Resolution

1

0x0405

1

 

 

24

r

Entering Condenser Water Temp. - Hi Resolution

1

0x041E

8

 

 

25

r

Entering Evaporator Water Temp. - Lo Resolution

1

0x0401

1

 

 

26

r

Entering Evaporator Water Temp. - Hi Resolution

1

0x041A

1

 

 

27

r

Entering Water Reset

1

0x0438

1

 

 

28

r

Evaporator Low Pressure Switch

1

0x050E

1

 

 

29

r

Evaporator Pump

1

0X021B

1

 

 

30

r

Evaporator Refrigerant Pressure

1

0x0410

1

 

 

31

r

Evaporator Refrigerant Temp. - Lo Resolution

1

0x0402

1

 

 

32

r

Evaporator Refrigerant Temp. - Hi Resolution

1

0x041B

7

 

 

33

r

Evaporator Water Flow Switch

1

0X050F

1

 

 

34

r

High Discharge Pressure Switch

1

0X050E

1

 

 

35

r

Hot Gas Solenoid

1

0x0212

1

 

 

36

r

Leaving Condenser Water Temp. - Lo Resolution

1

0x0406

1

 

 

37

r

Leaving Condenser Water Temp. - Hi Resolution

1

0x041F

8

 

 

38

r

Leaving Evaporator Water Temp. - Lo Resolution

1

0x0400

1

 

7See Appendix A.1.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldServer.com

Image 22
Contents Driver Manual FS-8700-80 McQuay Micro Tech Open Protocol Table of Contents Page McQuay Micro Tech Open Protocol Driver Manual Hardware Connections Provided by Supplier of 3rd Party EquipmentFieldServer Data Arrays Page Page Driver Related Map Descriptor Parameters Timing ParametersDACHILLER1 Map Descriptor Example 3 Write DamodesPage Page Driver Specific Map Descriptor Parameters DACHILLER1 Passive Chiller1 1024 256 Chiller1emulation2 Page Equipment Type 200CFC 200 Series Centrifugal Chiller McQuay Micro Tech Open Protocol Driver Manual Equipment Type 050RPC Reciprocating Chiller McQuay Micro Tech Open Protocol Driver Manual Page McQuay Micro Tech Open Protocol Driver Manual Equipment Type 001ASC Reciprocating Chiller Equipment Type Self-Contained Units SCUs McQuay Micro Tech Open Protocol Driver Manual Appendix A.3 McQuay Equipment Types recognized by the driver Appendix A.4. Direct AddressingPage DACHILLER1 DACHILLER1 NAK Damcqstats UINT32 Page McQuay Micro Tech Open Protocol Driver Manual Appendix C.3. Node ID problems Appendix C.2. Negative Acknowledgement NAK