McQuay Micro Tech Open Protocol Driver Manual | Page 33 of 35 |
Appendix B. Error Messages
Those messages marked with an * are only printed once even if they occur repeatedly.
Error Message | Action | |
McQuay:#1 FYI. The MapDesc | The length of the Map Descriptor used to expose driver statistics is | |
too short. Set the length to at least 1000. You can ignore this | ||
called <%s> is too short | ||
message – the driver will abandon excess statistics. | ||
| ||
McQuay:#2 FYI. You could | You can safely ignore this message. It is a prompt. Refer to | |
have used a MapDesc called | ||
Appendix A.8. | ||
<%s> to expose diagnostic info. | ||
McQuay:#3 FYI. Normally | This is a reminder that a password is expected when a node is | |
defined. Refer to sections 4.3 or 5.2. Even though password | ||
passwords are defined for each | ||
node. | checking is not enforced when the driver is configured as a Server, | |
the driver expects one to be defined for every node. | ||
| ||
McQuay:#4 Err. Node list if full. | A maximum of 100 McQuay device nodes can be configured per | |
Max=%d | FieldServer. If the limit is reached, call support. | |
| A node has been provided with two passwords. This is either a | |
| configuration error or two nodes with the same address are | |
McQuay:#5 Err. Node=%d has | connected to different ports. The driver can only store one password | |
more than one password. | per node address and cannot use the port number to differentiate | |
| them. | |
| if they have the same addresses. | |
*McQuay:#9 FYI. Device | Device Scaling is being applied and the driver doesn’t know how to | |
scale a variable. Please submit your configuration file with your | ||
scaling method unknown. | ||
request for support. | ||
| ||
McQuay:#10 Err. Node=%s. | The driver doesn’t recognize the equipment type specified using the | |
PLC_Type parameter in the configuration file. Refer to Appendix A.3 | ||
Equip. type not recognized. | ||
for a list of valid equipment types.10 | ||
McQuay:#11 Err. Node=%s. | Refer to Sections 4.3, 5.2. and Appendix A.310 | |
Equip. Type not specified. |
| |
McQuay:#13 Err. | Refer to Appendix A.2 for a list of valid field names. Refer also to | |
MapDesc=%s. Field Name | ||
Sections 4.4 or 5.3. | ||
unknown. | ||
| ||
McQuay:#14 Err. | Corrective action is required. When writing to a McQuay device using | |
MapDesc=%s. Max Len=1 for | ||
direct addressing the length may only be 110 | ||
Writes with direct addr. |
| |
McQuay:#15 Err. | Neither a field name nor an address was specified. The driver does | |
MapDesc=%s. Field | not know what location to read. Specify a field name from Appendix | |
Name/Address Required. | A.2.10 | |
McQuay:#16 Err. | Each Map Descriptor must be connected to a node. This is done by | |
MapDesc=%s. No Node. | specifying a node name. 10 | |
McQuay:#17 Err. | The offset added to the length of the Map Descriptor extends beyond | |
MapDesc=%s. Md too short. | the Data Array. Increase the Data Array length. 10 | |
McQuay:#18 Err. | When using ‘everything’ as a field name the Map Descriptor function | |
MapDesc=%s. Cannot write | ||
must be Rdbc or Rdb as this is a read only function.10 | ||
'Everything'. |
| |
McQuay:#19 do diagnostic 3 | Call FieldServer Technical Support. A developer diagnostic has been | |
McQuay:#20 do diagnostic 1 | ||
called and should not have been. | ||
McQuay:#21 do diagnostic 2 | ||
|
10Correct the configuration by editing the CSV file and downloading it to the FieldServer, then reset the FieldServer for the changes to take effect.