FieldServer FS-8700-80 instruction manual Equipment Type 050RPC Reciprocating Chiller

Page 20

McQuay Micro Tech Open Protocol Driver Manual

 

Page 20 of 35

 

 

 

 

 

 

 

 

 

Array

Read/

Field Name

Number

Base

Device

 

 

Write/

Scaling5

 

 

Location

of Bytes

Address

 

 

 

 

 

 

Both

 

 

 

Method

 

 

115

b

Communications Signal

1

0x047D

1

 

 

116

b

Outdoor Air Temperature - BAS

1

0x0473

5

 

 

117

b

Master/Server Setpoint

1

0x093C

1

 

 

118

b

Lead/Lag Mode Setpoint

1

0x093D

1

 

 

119

b

Enable Lag Setpoint

1

0x093E

1

 

 

120

b

Disable Lag Setpoint

1

0x093F

1

 

 

121

b

Lag Standby Setpoint

1

0x0942

1

 

 

122

b

Lead/Lag Switch Setpoint (Day)

1

0x0948

1

 

 

123

b

Lead/Lag Switch Setpoint (Hour)

1

0x0949

1

 

 

124

r

Lead/Lag Status

1

0x0401

1

 

 

125

r

Lead Unit

1

0x0402

1

 

 

126

r

Lead Unit Status

1

0x0403

1

 

 

127

r

Lag Unit Status

1

0x0404

1

 

 

128

r

Lead Motor Current

1

0x0405

1

 

 

129

r

Lag Motor Current

1

0x0406

1

 

 

130

r

Lead Status

1

0x0407

1

 

 

131

r

Lag Status

1

0x0408

1

 

 

132

b

Chiller Control mode

1

0x900

1

 

 

133

b

Chilled Water Temperature Local Setpoint

1

0x901

4

 

 

134

r

Chilled Water Temperature – Active Setpoint

1

0x905

4

 

Table 3 - Equipment Type: 050RPC Reciprocating Chiller

Array

Read/

 

Number

Base

Device

Write/

Field Name

Scaling6

Location

of Bytes

Address

 

 

 

Both

 

 

 

Method

3

r

Circuit #1 Condenser Approach Temperature

2

0x0497

2

5

r

Circuit #1 Condenser Pressure

2

0x0467

2

7

r

Circuit #1 Alarm Conditions: Condenser Pressure

2

0x0822

2

9

r

Circuit #1 Alarm Conditions: Evaporator Pressure

2

0x0820

2

11

r

Circuit #1 Alarm Conditions: Liquid Line Temp

2

0x0826

6

13

r

Circuit #1 Alarm Conditions: Suction Temperature

2

0x0824

6

14

r

Circuit #1 Current Alarm

1

0x0831

1

16

r

Circuit #1 Evaporator Pressure

2

0x0463

2

18

r

Circuit #1 Liquid Line Temperature

2

0x0479

6

19

r

Circuit #1 Previous Alarm

1

0x0833

1

20

r

Circuit #1 Status

1

0x0428

1

22

r

Circuit #1 Subcooling Temperature

2

0x049B

2

24

r

Circuit #1 Suction Temperature

2

0x0475

6

26

r

Circuit #1 Superheat Temperature

2

0x0493

2

28

r

Circuit #2 Condenser Approach Temperature

2

0x0499

2

6See Appendix A.1.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldServer.com

Image 20
Contents Driver Manual FS-8700-80 McQuay Micro Tech Open Protocol Table of Contents Page McQuay Micro Tech Open Protocol Driver Manual FieldServer Provided by Supplier of 3rd Party EquipmentHardware Connections Data Arrays Page Page Driver Related Map Descriptor Parameters Timing ParametersDACHILLER1 Map Descriptor Example 3 Write DamodesPage Page Driver Specific Map Descriptor Parameters DACHILLER1 Passive Chiller1 1024 256 Chiller1emulation2 Page Equipment Type 200CFC 200 Series Centrifugal Chiller McQuay Micro Tech Open Protocol Driver Manual Equipment Type 050RPC Reciprocating Chiller McQuay Micro Tech Open Protocol Driver Manual Page McQuay Micro Tech Open Protocol Driver Manual Equipment Type 001ASC Reciprocating Chiller Equipment Type Self-Contained Units SCUs McQuay Micro Tech Open Protocol Driver Manual Appendix A.3 McQuay Equipment Types recognized by the driver Appendix A.4. Direct AddressingPage DACHILLER1 DACHILLER1 NAK Damcqstats UINT32 Page McQuay Micro Tech Open Protocol Driver Manual Appendix C.3. Node ID problems Appendix C.2. Negative Acknowledgement NAK