FieldServer FS-8700-80 instruction manual Equipment Type 200CFC 200 Series Centrifugal Chiller

Page 18

McQuay Micro Tech Open Protocol Driver Manual

Page 18 of 35

Appendix A.2. Data Field Name Tables

If you do not know the field name it is possible to read the device by specifying the address only. More information is provided in Appendix A.4

Table 2 – Equipment Type: 200CFC 200 Series Centrifugal Chiller

Array

Read/

Field Name

Number

Base

Device

Write/

Scaling5

Location

of Bytes

Address

 

 

 

Both

 

 

 

Method

1

r

Model

3

0x0A08

1

4

r

Refrigerant

1

0x0A0B

1

5

r

Units of Measure

1

0x0A0C

1

6

r

Software Version

2

0x0A0D

1

8

r

Software Revision

1

0x0A0F

1

11

r

Chiller Unit Temperature Type

1

0x084B

1

12

r

Communication Status

1

0x040C

1

13

r

Compressor Lift Pressure

2

0x046A

2

15

r

Compressor Motor Current

2

0x044C

1

17

r

Compressor Motor Current Percent

1

0x044A

1

18

r

Compressor Number of Starts

2

0x085F

1

20

r

Compressor Operating Hours

2

0x0851

1

22

r

Compressor Suction Temperature

2

0x043A

3

24

r

Compressor Superheat - Discharge

2

0x046E

2

26

r

Compressor Superheat -Suction

2

0x046C

2

28

r

Condenser Approach Temperature

2

0x0484

2

30

r

Condenser Heat Recovery Unit Present

1

0x083F

1

31

r

Condenser Heat Recovery Temperature - Delta

2

0x048A

2

33

r

Condenser Heat Recovery Water Temp. - Entering

2

0x0454

3

35

r

Condenser Heat Recovery Water Temp. - Leaving

2

0x0456

3

37

r

Condenser Pump Status

1

0x0425

1

38

r

Condenser Pump # 1 Operating Hours

2

0x085A

1

40

r

Condenser Pump # 2 Operating Hours

2

0x085D

1

42

r

Condenser Refrigerant Pressure

2

0x0440

2

44

r

Condenser Refrigerant Temperature

2

0x0466

3

46

r

Condenser Subcooling Temperature

2

0x0480

2

48

r

Condenser Water Flow Rate

2

0x0452

1

50

r

Condenser Water Flow Status

1

0x045F

1

51

r

Condenser Water Rate Sensor

1

0x083D

1

52

r

Condenser Water Temperature - Delta

2

0x0488

2

54

r

Condenser Water Temperature - Entering

2

0x0436

3

Additional information may be obtained from McQuay International. Request the following document. MicroTech® Series 200 Centrifugal Chiller Data Communications Packet for Open Protocol™ Cent2_22.doc

5See Appendix A.1.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldServer.com

Image 18
Contents Driver Manual FS-8700-80 McQuay Micro Tech Open Protocol Table of Contents Page McQuay Micro Tech Open Protocol Driver Manual Provided by Supplier of 3rd Party Equipment Hardware ConnectionsFieldServer Data Arrays Page Page Driver Related Map Descriptor Parameters Timing ParametersDACHILLER1 Map Descriptor Example 3 Write DamodesPage Page Driver Specific Map Descriptor Parameters DACHILLER1 Passive Chiller1 1024 256 Chiller1emulation2 Page Equipment Type 200CFC 200 Series Centrifugal Chiller McQuay Micro Tech Open Protocol Driver Manual Equipment Type 050RPC Reciprocating Chiller McQuay Micro Tech Open Protocol Driver Manual Page McQuay Micro Tech Open Protocol Driver Manual Equipment Type 001ASC Reciprocating Chiller Equipment Type Self-Contained Units SCUs McQuay Micro Tech Open Protocol Driver Manual Appendix A.3 McQuay Equipment Types recognized by the driver Appendix A.4. Direct AddressingPage DACHILLER1 DACHILLER1 NAK Damcqstats UINT32 Page McQuay Micro Tech Open Protocol Driver Manual Appendix C.3. Node ID problems Appendix C.2. Negative Acknowledgement NAK