FieldServer FS-8700-80 instruction manual Equipment Type Self-Contained Units SCUs

Page 25

McQuay Micro Tech Open Protocol Driver Manual

 

 

 

Page 25 of 35

 

 

 

 

 

 

 

 

 

 

 

 

 

Array

Read/

 

Number

Base

Device

 

 

 

Write/

Field Name

Scaling8

 

 

 

Location

of Bytes

Address

 

 

 

 

 

 

 

Both

 

 

 

 

 

Method

 

 

 

43

b

Clear Ckt#1 Alarm

1

0x091A

 

1

 

 

 

44

b

Evaporator Entering Water Temperature Setpoint

1

0x090D

 

2

 

 

 

45

b

Evaporator Leaving Water Temperature Setpoint

1

0x0905

 

2

 

 

 

46

b

Maximum Chilled Water Reset Setpoint

1

0x090C

 

2

 

 

 

47

b

Network Command

1

0x044F

 

1

 

 

 

48

b

Network Demand Limit

1

0x044D

 

1

 

 

 

49

b

Network Evaporator Leaving Water Temp Reset

1

0x044E

 

1

 

 

 

50

b

Reset Option Setpoint

1

0x090B

 

1

 

 

Table 6 - Equipment Type : Self-Contained Units (SCUs)

 

 

 

 

 

 

 

 

 

Array

Read/

 

 

Number

Base

 

Device

 

 

Write/

Field Name

 

 

Scaling9

 

 

Location

 

of Bytes

Address

 

 

 

 

 

 

 

Both

 

 

 

 

 

 

Method

 

 

1

r

Air Velocity

 

1

 

0x0434

1

 

 

 

2

r

Airflow Status

 

1

 

0x045C

1

 

 

 

3

r

Current Alarm

 

1

 

0x0801

1

 

 

 

4

r

Previous Alarm

 

1

 

0x1301

1

 

 

 

5

r

Building Static Pressure

 

1

 

0x0435

1

 

 

 

6

r

Compressor #1 Alarm

 

1

 

0x081C

1

 

 

 

7

r

Compressor #1 Operating Hours

 

2

 

0x08AF

1

 

 

 

9

r

Compressor #2 Alarm

 

1

 

0x081D

1

 

 

 

10

r

Compressor #2 Operating Hours

 

2

 

0x08B2

1

 

 

 

12

r

Compressor #3 Alarm

 

1

 

0x081E

1

 

 

 

13

r

Compressor #3 Operating Hours

 

2

 

0x08B5

1

 

 

 

15

r

Compressor #4 Alarm

 

1

 

0x081F

1

 

 

 

16

r

Compressor #4 Operating Hours

 

2

 

0x08B8

1

 

 

 

18

r

Compressor #5 Alarm

 

1

 

0x0820

1

 

 

 

19

r

Compressor #5 Operating Hours

 

2

 

0x08BB

1

 

 

 

21

r

Compressor #6 Alarm

 

1

 

0x0821

1

 

 

 

22

r

Compressor #6 Operating Hours

 

2

 

0x08BE

1

 

 

 

24

r

Control Temperature

 

1

 

0x0432

1

 

 

 

25

r

Cool Stage

 

1

 

0x043F

1

 

 

 

26

r

Cooling Control Status

 

1

 

0x044A

1

 

 

 

27

r

Dew Point Temperature

 

1

 

0x042F

1

 

 

 

28

r

Duct Static Pressure #1

 

1

 

0x0435

1

 

 

 

29

r

Duct Static Pressure #2

 

1

 

0x0434

1

 

 

 

30

r

Economizer Enable

 

1

 

0x045A

1

 

 

 

31

r

Economizer Operating Hours

 

2

 

0x08C4

1

 

 

 

33

r

Economizer Position

 

1

 

0x042E

1

 

 

 

34

r

Entering Water Temperature

 

1

 

0x042C

1

 

 

9See Appendix A.1.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldServer.com

Image 25
Contents Driver Manual FS-8700-80 McQuay Micro Tech Open Protocol Table of Contents Page McQuay Micro Tech Open Protocol Driver Manual Hardware Connections Provided by Supplier of 3rd Party EquipmentFieldServer Data Arrays Page Page Timing Parameters Driver Related Map Descriptor ParametersDACHILLER1 Damodes Map Descriptor Example 3 WritePage Page Driver Specific Map Descriptor Parameters DACHILLER1 Passive Chiller1 1024 256 Chiller1emulation2 Page Equipment Type 200CFC 200 Series Centrifugal Chiller McQuay Micro Tech Open Protocol Driver Manual Equipment Type 050RPC Reciprocating Chiller McQuay Micro Tech Open Protocol Driver Manual Page McQuay Micro Tech Open Protocol Driver Manual Equipment Type 001ASC Reciprocating Chiller Equipment Type Self-Contained Units SCUs McQuay Micro Tech Open Protocol Driver Manual Appendix A.4. Direct Addressing Appendix A.3 McQuay Equipment Types recognized by the driverPage DACHILLER1 DACHILLER1 NAK Damcqstats UINT32 Page McQuay Micro Tech Open Protocol Driver Manual Appendix C.2. Negative Acknowledgement NAK Appendix C.3. Node ID problems