FieldServer FS-8700-80 Appendix C.2. Negative Acknowledgement NAK, Appendix C.3. Node ID problems

Page 35

McQuay Micro Tech Open Protocol Driver Manual

Page 35 of 35

Appendix C. Troubleshooting

Appendix C.1. Connection Problems

The driver produces a timeout each time a message is sent. If the number of timeouts is the same as the number of messages sent then you know that the McQuay device has never sent a response. The following reasons may be applicable:

Incorrect connection settings - the messages sent by the FieldServer cannot be interpreted by the McQuay device.

Incorrect connection wiring – the McQuay device may require a jumper on its serial port to deflect hardware handshaking. Refer to the vendor manual.

Serial port failure – If the Tx LED is not flashing each time a message is sent, the port is not working

The McQuay device is off.

If the Node_ID and Route are incorrect, the McQuay device will not respond at all.

Appendix C.2. Negative Acknowledgement - NAK

The Server sends a NAK message and increments the NAK stat each time a poll is unsuccessful. An occasional NAK may indicate a corrupted message. If the number of NAK's is the same as the number of transmitted messages to a Node, however, one of the following problems could apply:

Bad Password - the password specified in the "read" command did not match any of the access level passwords stored in the MicroTech controller to which the terminal is connected. Call FST Tech support for default passwords or call your Vendor. FST recommends checking the password first as in almost all reports the problem was resolved by changing the password.

Device has been polled with an invalid command code.

Bad Node_ID / Route parameters for the node.

The MCQ device received the message and thought it was badly formatted. This is unlikely on a repeated basis unless the connection settings were slightly wrong.

The packet structure was invalid

The packet was received with a parity or framing error

Appendix C.3. Node ID problems

If the Node is incorrectly specified, the FieldServer will not get a response from the McQuay unit. The ID used to communicate with the McQuay unit needs to be determined. This may not be the same as shown on the Rotary switches of the unit. Note that McQuay uses Hexadecimal notation for addressing, therefore, if connection to the Unit is with address 0201, this is in Hex and the Node ID for the FieldServer configuration needs to be 513.

Appendix C.4. Server Side Configuration – Consecutive Addresses

Some variables have their values stored in two consecutive address locations. When the Client polls for the value it actually sends two read messages – one for each address. When configuring the Server side, therefore, it is necessary to define two Map Descriptors for variables which require two consecutive addresses.

Map_Descriptors

 

 

 

 

 

 

Map_Descriptor_Name

,Data_Array_Name

,Data_Array_Offset

,Function

,Node_Name

,Address

,Length

Supply Fan Status

,DA_AI_01

,01

,Passive

,Node_A

,1118

,1

Supply Temp

,DA_AI_01

,02

,Passive

,Node_A

,1063

,1

Space Temp

,DA_AI_01

,03

,Passive

,Node_A

,1066

,1

Control Temp Part 1

,DA_AI_01

,04

,Passive

,Node_A

,1074

,1

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldServer.com

Image 35
Contents Driver Manual FS-8700-80 McQuay Micro Tech Open Protocol Table of Contents Page McQuay Micro Tech Open Protocol Driver Manual FieldServer Provided by Supplier of 3rd Party EquipmentHardware Connections Data Arrays Page Page Timing Parameters Driver Related Map Descriptor ParametersDACHILLER1 Damodes Map Descriptor Example 3 WritePage Page Driver Specific Map Descriptor Parameters DACHILLER1 Passive Chiller1 1024 256 Chiller1emulation2 Page Equipment Type 200CFC 200 Series Centrifugal Chiller McQuay Micro Tech Open Protocol Driver Manual Equipment Type 050RPC Reciprocating Chiller McQuay Micro Tech Open Protocol Driver Manual Page McQuay Micro Tech Open Protocol Driver Manual Equipment Type 001ASC Reciprocating Chiller Equipment Type Self-Contained Units SCUs McQuay Micro Tech Open Protocol Driver Manual Appendix A.4. Direct Addressing Appendix A.3 McQuay Equipment Types recognized by the driverPage DACHILLER1 DACHILLER1 NAK Damcqstats UINT32 Page McQuay Micro Tech Open Protocol Driver Manual Appendix C.2. Negative Acknowledgement NAK Appendix C.3. Node ID problems