FieldServer FS-8700-21 instruction manual Domain Table Setup

Page 15

FS-8700-21 LonWorks Manual

Page 15 of 62

 

 

6.1.4 Domain Table Setup

To be able to communicate with other nodes on the LonWorks network, the FieldServer must have its Domain, Subnet and Node ID’s set. Explicit configuration requires the user to set these parameters.

There are 3 ways in which the FieldServer DSN (Domain,Subnet,Node address) can be set:

Set the DSN using a Network manager by commissioning the FieldServer into the Network Manager Project. When doing it this way, it is extremely important that the DSN is not forced in the FieldServer Configuration, as the Configuration address will override the Network Manager Address every time the FieldServer is restarted.

Set the DSN from the Lon.ini file. Using this option provides a default DSN if the FieldServer does not have a DSN assigned. If a Network Manager or the FieldServer Configuration provides a DSN, then the Lon.ini DSN will be ignored.

Set the DSN in the FieldServer configuration. This option takes precedence over the 2 other addressing options, and should therefore not be used when commissioning a FieldServer into a Network with a Network Manager.

Example 1 - Setting the Domain and Subnet from the lon.ini file

The Domain Table and Subnet IDs can be set from a lon.ini file on the FieldServer. The FieldServer’s LonWorks Node ID will be set from the System_Station_Address field in the configuration file if specified, otherwise a default value will be used.

lon.ini file contents: :D50:S01:

FieldServer configuration file contents ( config.csv )

FieldServer

System_Station_Address ,Title

12

 

,Your title

 

 

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

Image 15
Contents Driver Manual FS-8700-21 LonWorks Table of Contents Appendix D. SNVTType NV Updates/Polls Network ManagementLonWorks Program ID Calculation Spid XIF Files Configuration PropertiesClients/Servers Explicit/ImplicitSupplied by FieldServer Technologies for this driver Provided by the Supplier of 3 rd Party EquipmentAdditional files required for the Driver Hardware Connections Service PinLonWorks Adapter Card FS-X40 only Port Address SwitchNeuron ID Lon LED’sSNVTIndex Special considerationsMap Descriptor Names Network Variable Names Implicit Lon functionsNetwork Management Capability Client vs Server MappingClient Side Mapping Connection Parameters FieldServer Related Map Descriptor Parameters Node ParametersTiming Parameters Driver Related Map Descriptor ParametersClient Side Map Descriptor Example Lon functions Explicit ConfigurationsDomain Table Setup Network Management Nodes Client Side Configuration ConnectionsFS-8700-21 LonWorks ManualPage 18 Map Descriptor Example 2 Polling UNVT’s Using Neuron ID to Address Devices Client Drivers only Server Side Configuration Connections FS-8700-21 LonWorks ManualPage 22 Map Descriptor Example Appendix A.4. XIF Generation Appendix A.1. Using UNVT’sAppendix A.2. Using NVMin, NVMax etc Appendix A.3. Throttling ModeAppendix A.6. LonMark Object Creation Appendix A.5. Configuration PropertiesCfgnvui Appendix A.8. Working with Binary Data Appendix A.7. Node Status OperationAppendix A.9. Filtering Snvt Variables FS-8700-21 LonWorks Manual Appendix B.1. Echelon LonMaker Appendix B. Vendor InformationAppendix B.2. Neuron Systems Appendix B.3. Honeywell CareAppendix B.4. Tridium Jace Appendix B.5. Trane Rover Appendix C.1. Debugging a LonWorks connection Hints and tips Appendix C.2. Error MessagesUINT32 Appendix C.3. Exposing Operation StatisticsAppendix C.4. Illegal Characters in Network Variable Names Appendix C.5. CirconSI LimitationsAppendix C.7. Combining Explicit and Implicit Appendix D. SNVTType Location array element Kilo-British Thermal 65,535 Units Mega-British Thermal Sender Range Lower ID Data Length Suggested Data Array Formats KiloJoules per Kilogram FS-8700-21 LonWorks Manual Data Length Suggested Data Array Formats Float Measurement Units Values Range Invalid Value 163.840 Type Raw SNVTmassf FS-8700-21 LonWorks Manual Data Item Measurement Units Values Range Invalid Value Parts per Million ppm FS-8700-21 LonWorks Manual Measurement Units Values Range Invalid Value SNVTpumpsensor SNVTpumpsetmn Measurement Units Values Range Invalid Value SNVTpumpsetmn SNVTpwrfactf RPM Millimeters per Second Difference Type Measurement Units Values Range Invalid Value SNVTtempsetpt FS-8700-21 LonWorks Manual Kiloliters kl Measurement Units Values Range Invalid Value SNVTzerospan