FieldServer FS-8700-21 instruction manual Appendix A.5. Configuration Properties

Page 25

FS-8700-21 LonWorks Manual

Page 25 of 62

 

 

Appendix A.5. Configuration Properties

Configuration Properties are implemented on the FieldServer using configuration Network Variables. Configuration Network Variables take the form of update inputs in order to be updated or read by a network management tool. Each Configuration Network Variable will have its own Map Descriptor. Since the data carried by a Network Variable is intended as a configuration property for other already declared non-configuration Network Variable(s), no Data Array needs to be assigned to its Map Descriptor.

Configuration Properties can be declared to belong to the entire Node, to an Object(s) or to a Network Variable(s). This declaration defines the scope of the Configuration Property. Configuration Properties that belong to an Object are declared as a part of the Object; Configuration Properties associated with a Network Variable(s) are declared as belonging to the Network Variable(s) etc.

A Configuration Property’s Type and Responsible Map Descriptor(s) are declared by the Configuration Network Variable’s self-documentation string as follows:

For linking to the entire node: “&0,,0\x80,*SCPT Index+” Example: “&0,,0\x80,20”

For linking to object(s):

“&1,[Object Index(s)],0\x80,*SCPT Index+” Example: “&1,0.2.3,0\x80,23”

For linking to network variable(s): “&2,*NV Index(s)+,0\x80,*SCPT Index+” Example: “&2,0.1.2.4.7,0\x80,20”

Examples of configuration network variables are presented in Section 6.3.6

Appendix A.6. LonMark Object Creation

For more information on filling out the Node Self-Documentation String as well as the relevant Network Variable Self- Documentation Strings in order to create a LonMark Object please consult the following documentation from the LonMark Interoperability Association at www.lonmark.org

Understanding LonMark Self-Documentation

LonMark Application Layer Interoperability Guidelines

The two examples given below will show how LonMark Objects can be assigned in FieldServer configuration files:

The first example uses the standard Open Loop Sensor Object (Type 1) to create a Water Temperature Sensor that will send out its current status via Network Variable Updates.

A typical recipient of these updates is given by example #2 which uses the LonMark Open Loop Actuator Object (Type 3) to create a Water Heating Element object that will interpret the Network Variable it receives and adjust power to its heating element accordingly.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

Image 25
Contents Driver Manual FS-8700-21 LonWorks Table of Contents Appendix D. SNVTType Network Management NV Updates/PollsLonWorks Program ID Calculation Spid Clients/Servers Configuration PropertiesExplicit/Implicit XIF FilesProvided by the Supplier of 3 rd Party Equipment Supplied by FieldServer Technologies for this driverAdditional files required for the Driver Hardware Connections Service PinNeuron ID Port Address SwitchLon LED’s LonWorks Adapter Card FS-X40 onlyMap Descriptor Names Network Variable Names Special considerationsImplicit Lon functions SNVTIndexClient vs Server Mapping Network Management CapabilityClient Side Mapping Connection Parameters FieldServer Related Map Descriptor Parameters Node ParametersTiming Parameters Driver Related Map Descriptor ParametersClient Side Map Descriptor Example Lon functions Explicit ConfigurationsDomain Table Setup Network Management Nodes Client Side Configuration ConnectionsFS-8700-21 LonWorks ManualPage 18 Map Descriptor Example 2 Polling UNVT’s Using Neuron ID to Address Devices Client Drivers only Server Side Configuration Connections FS-8700-21 LonWorks ManualPage 22 Map Descriptor Example Appendix A.2. Using NVMin, NVMax etc Appendix A.1. Using UNVT’sAppendix A.3. Throttling Mode Appendix A.4. XIF GenerationAppendix A.6. LonMark Object Creation Appendix A.5. Configuration PropertiesCfgnvui Appendix A.8. Working with Binary Data Appendix A.7. Node Status OperationAppendix A.9. Filtering Snvt Variables FS-8700-21 LonWorks Manual Appendix B.1. Echelon LonMaker Appendix B. Vendor InformationAppendix B.3. Honeywell Care Appendix B.2. Neuron SystemsAppendix B.4. Tridium Jace Appendix B.5. Trane Rover Appendix C.1. Debugging a LonWorks connection Hints and tips Appendix C.2. Error MessagesUINT32 Appendix C.3. Exposing Operation StatisticsAppendix C.5. CirconSI Limitations Appendix C.4. Illegal Characters in Network Variable NamesAppendix C.7. Combining Explicit and Implicit Appendix D. SNVTType Location array element Kilo-British Thermal 65,535 Units Mega-British Thermal Sender Range Lower ID Data Length Suggested Data Array Formats KiloJoules per Kilogram FS-8700-21 LonWorks Manual Data Length Suggested Data Array Formats Float Measurement Units Values Range Invalid Value 163.840 Type Raw SNVTmassf FS-8700-21 LonWorks Manual Data Item Measurement Units Values Range Invalid Value Parts per Million ppm FS-8700-21 LonWorks Manual Measurement Units Values Range Invalid Value SNVTpumpsensor SNVTpumpsetmn Measurement Units Values Range Invalid Value SNVTpumpsetmn SNVTpwrfactf RPM Millimeters per Second Difference Type Measurement Units Values Range Invalid Value SNVTtempsetpt FS-8700-21 LonWorks Manual Kiloliters kl Measurement Units Values Range Invalid Value SNVTzerospan