FieldServer FS-8700-21 Measurement Units Values Range Invalid Value SNVTtempsetpt

Page 59

 

FS-8700-21 LonWorks Manual

 

 

 

 

 

 

 

 

 

Page 59 of 62

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data Length

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

Suggested Data Array Formats

 

 

 

 

 

 

Float

 

 

 

 

SNVT_temp_f

 

 

Data Item 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Measurement

 

 

Units

 

 

Values Range

 

 

 

Invalid Value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Incremental Count

 

Degrees Celcius

 

 

-3.40282E38 ..

 

 

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

3.40282E38

 

 

 

 

 

 

 

 

 

 

 

Data Length

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

Suggested Data Array Formats

 

 

 

 

 

 

Float

 

 

 

 

SNVT_temp_p

 

 

Data Item 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Measurement

 

 

Units

 

 

Values Range

 

 

 

Invalid Value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature

 

 

Degrees celsius

 

-273.17 .. 327.66

 

 

Type: 327.67

Raw: 32,767

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(0x7FFF)

 

 

 

 

 

 

 

Data Length

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

Suggested Data Array Formats

 

 

 

 

 

 

Float

 

 

 

 

SNVT_temp_ror

 

 

Data Item 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Measurement

 

 

Units

 

 

Values Range

 

 

 

Invalid Value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature

Rate of

 

Degrees Celsius

per

-16,384.0

..

 

 

Raw: 32,767 (0x7FFF)

 

 

 

 

 

Change/Rise

 

 

Minute (˚C/min)

 

16,383.0

 

 

 

Type: 16,383.5

 

 

 

 

 

 

 

Data Length

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

Suggested Data Array Formats

 

 

 

 

 

 

Float

 

 

 

 

 

 

 

Data Item 1

 

 

 

 

 

 

 

 

 

Occupied_cool

 

 

 

 

 

 

 

Measurement

 

 

Units

 

 

Values Range

 

 

 

Invalid Value

 

 

 

 

 

 

 

Occupied

Cooling

 

Degrees Celsius

 

-273.17 .. 327.66

 

 

Type: 327.67

Raw: 32,767

 

 

 

 

 

Setpoint

 

 

 

 

 

 

 

 

 

(0x7FFF)

 

 

 

 

 

 

 

Data Item 2

 

 

 

 

 

 

 

 

 

Standby_cool

 

 

 

 

 

 

 

Measurement

 

 

Units

 

 

Values Range

 

 

 

Invalid Value

 

 

 

 

 

 

 

Standby

Cooling

 

Degrees Celsius

 

-273.17 .. 327.66

 

 

Type: 327.67

Raw: 32,767

 

 

 

 

 

Setpoint

 

 

 

 

 

 

 

 

 

(0x7FFF)

 

 

 

 

 

 

 

Data Item 3

 

 

 

 

 

 

 

 

 

Unoccupied_cool

 

 

 

 

 

 

Measurement

 

 

Units

 

 

Values Range

 

 

 

Invalid Value

 

 

 

 

SNVT_temp_setpt

 

 

Unoccupied

Cooling

 

Degrees Celsius

 

-273.17 .. 327.66

 

 

Type: 327.67

Raw: 32,767

 

 

 

 

Setpoint

 

 

 

 

 

 

 

 

 

(0x7FFF)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data Item 4

 

 

 

 

 

 

 

 

 

Occupied_heat

 

 

 

 

 

 

 

Measurement

 

 

Units

 

 

Values Range

 

 

 

Invalid Value

 

 

 

 

 

 

 

Occupied

Heating

 

Degrees Celsius

 

-273.17 .. 327.66

 

 

Type: 327.67

Raw: 32,767

 

 

 

 

 

Setpoint

 

 

 

 

 

 

 

 

 

(0x7FFF)

 

 

 

 

 

 

 

Data Item 5

 

 

 

 

 

 

 

 

 

Standby_heat

 

 

 

 

 

 

 

Measurement

 

 

Units

 

 

Values Range

 

 

 

Invalid Value

 

 

 

 

 

 

 

Standby

Heating

 

Degrees Celsius

 

-273.17 .. 327.66

 

 

Type: 327.67

Raw: 32,767

 

 

 

 

 

Setpoint

 

 

 

 

 

 

 

 

 

(0x7FFF)

 

 

 

 

 

 

 

Data Item 6

 

 

 

 

 

 

 

 

 

Unoccupied_heat

 

 

 

 

 

 

Measurement

 

 

Units

 

 

Values Range

 

 

 

Invalid Value

 

 

 

 

 

 

 

Unoccupied

Heating

 

Degrees Celsius

 

-273.17 .. 327.66

 

 

Type: 327.67

Raw: 32,767

 

 

 

 

 

Setpoint

 

 

 

 

 

 

 

 

 

(0x7FFF)

 

 

 

 

 

 

 

Data Length

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

Suggested Data Array Formats

 

 

 

 

 

 

Byte, Uint16, Float

 

 

SNVT_therm_mode

 

 

Data Item 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Measurement

 

 

Units

 

 

Values Range

 

 

 

Invalid Value

 

 

 

 

 

 

 

therm_mode_t

 

N/A

 

0 .. 2

 

 

 

255 (0xFF)(THERM_NUL)

 

 

 

 

 

Data Length

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

Suggested Data Array Formats

 

 

 

 

 

 

Float

 

 

 

 

SNVT_time_f

 

 

Data Item 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Measurement

 

 

Units

 

 

Values Range

 

 

 

Invalid Value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Elapsed Time

 

 

Seconds

 

 

-3.40282E38 ..

 

 

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

3.40282E38

 

 

 

 

 

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

Image 59
Contents Driver Manual FS-8700-21 LonWorks Table of Contents Appendix D. SNVTType LonWorks Program ID Calculation Spid NV Updates/PollsNetwork Management XIF Files Configuration PropertiesClients/Servers Explicit/ImplicitAdditional files required for the Driver Supplied by FieldServer Technologies for this driverProvided by the Supplier of 3 rd Party Equipment Hardware Connections Service PinLonWorks Adapter Card FS-X40 only Port Address SwitchNeuron ID Lon LED’sSNVTIndex Special considerationsMap Descriptor Names Network Variable Names Implicit Lon functionsClient Side Mapping Connection Parameters Network Management CapabilityClient vs Server Mapping FieldServer Related Map Descriptor Parameters Node ParametersTiming Parameters Driver Related Map Descriptor ParametersClient Side Map Descriptor Example Lon functions Explicit ConfigurationsDomain Table Setup Network Management Nodes Client Side Configuration ConnectionsFS-8700-21 LonWorks ManualPage 18 Map Descriptor Example 2 Polling UNVT’s Using Neuron ID to Address Devices Client Drivers only Server Side Configuration Connections FS-8700-21 LonWorks ManualPage 22 Map Descriptor Example Appendix A.4. XIF Generation Appendix A.1. Using UNVT’sAppendix A.2. Using NVMin, NVMax etc Appendix A.3. Throttling ModeAppendix A.6. LonMark Object Creation Appendix A.5. Configuration PropertiesCfgnvui Appendix A.8. Working with Binary Data Appendix A.7. Node Status OperationAppendix A.9. Filtering Snvt Variables FS-8700-21 LonWorks Manual Appendix B.1. Echelon LonMaker Appendix B. Vendor InformationAppendix B.4. Tridium Jace Appendix B.2. Neuron SystemsAppendix B.3. Honeywell Care Appendix B.5. Trane Rover Appendix C.1. Debugging a LonWorks connection Hints and tips Appendix C.2. Error MessagesUINT32 Appendix C.3. Exposing Operation StatisticsAppendix C.7. Combining Explicit and Implicit Appendix C.4. Illegal Characters in Network Variable NamesAppendix C.5. CirconSI Limitations Appendix D. SNVTType Location array element Kilo-British Thermal 65,535 Units Mega-British Thermal Sender Range Lower ID Data Length Suggested Data Array Formats KiloJoules per Kilogram FS-8700-21 LonWorks Manual Data Length Suggested Data Array Formats Float Measurement Units Values Range Invalid Value 163.840 Type Raw SNVTmassf FS-8700-21 LonWorks Manual Data Item Measurement Units Values Range Invalid Value Parts per Million ppm FS-8700-21 LonWorks Manual Measurement Units Values Range Invalid Value SNVTpumpsensor SNVTpumpsetmn Measurement Units Values Range Invalid Value SNVTpumpsetmn SNVTpwrfactf RPM Millimeters per Second Difference Type Measurement Units Values Range Invalid Value SNVTtempsetpt FS-8700-21 LonWorks Manual Kiloliters kl Measurement Units Values Range Invalid Value SNVTzerospan