FieldServer FS-8700-21 Appendix C.1. Debugging a LonWorks connection Hints and tips

Page 33

FS-8700-21 LonWorks Manual

Page 33 of 62

 

 

Appendix C. Troubleshooting Tips

Appendix C.1. Debugging a LonWorks connection: Hints and tips

To test connections, set the configuration tool into a mode that will display service requests, and then push the button on the FieldServer. A request should appear.

In order for variables to appear as outputs, they need to be declared as write variables in the FieldServer. Declaring the Map Descriptor functions as WRBC, or WRBX can do this. See Section 5.1.2 for more information.

If the domain and Subnet ID are defined in the configuration file of the FieldServer, these values will be used when power is cycled to the FieldServer. If the values set here are different to what the Network Manager has set up for the FieldServer for clients using implicit addressing, the FieldServer will stop communicating. In this case, change these settings or remove them from the configuration file completely and recommission the FieldServer.

Appendix C.2. Error Messages

Message

Description

"LON:#03 FYI. Standard driver build. This is normal.

This message is informational and can be safely ignored.

 

 

Appendix C.2.1. Error Message Lonlive.c 121

If the following error message is returned:

--------DRIVER-> LON : Error, timeout while waiting for Lon I/F to reset!

Configuration Error ------

 

 

It is possible that the FieldServer hardware in use may not support LonWorks, or the firmware loaded contains LonWorks but is the wrong firmware for the application. Remove LonWorks from the configuration or get new firmware/hardware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

Image 33
Contents Driver Manual FS-8700-21 LonWorks Table of Contents Appendix D. SNVTType NV Updates/Polls Network ManagementLonWorks Program ID Calculation Spid Clients/Servers Configuration PropertiesExplicit/Implicit XIF FilesSupplied by FieldServer Technologies for this driver Provided by the Supplier of 3 rd Party EquipmentAdditional files required for the Driver Hardware Connections Service PinNeuron ID Port Address SwitchLon LED’s LonWorks Adapter Card FS-X40 onlyMap Descriptor Names Network Variable Names Special considerationsImplicit Lon functions SNVTIndexNetwork Management Capability Client vs Server MappingClient Side Mapping Connection Parameters FieldServer Related Map Descriptor Parameters Node ParametersTiming Parameters Driver Related Map Descriptor ParametersClient Side Map Descriptor Example Lon functions Explicit ConfigurationsDomain Table Setup Network Management Nodes Client Side Configuration ConnectionsFS-8700-21 LonWorks ManualPage 18 Map Descriptor Example 2 Polling UNVT’s Using Neuron ID to Address Devices Client Drivers only Server Side Configuration Connections FS-8700-21 LonWorks ManualPage 22 Map Descriptor Example Appendix A.2. Using NVMin, NVMax etc Appendix A.1. Using UNVT’sAppendix A.3. Throttling Mode Appendix A.4. XIF GenerationAppendix A.6. LonMark Object Creation Appendix A.5. Configuration PropertiesCfgnvui Appendix A.8. Working with Binary Data Appendix A.7. Node Status OperationAppendix A.9. Filtering Snvt Variables FS-8700-21 LonWorks Manual Appendix B.1. Echelon LonMaker Appendix B. Vendor InformationAppendix B.2. Neuron Systems Appendix B.3. Honeywell CareAppendix B.4. Tridium Jace Appendix B.5. Trane Rover Appendix C.1. Debugging a LonWorks connection Hints and tips Appendix C.2. Error MessagesUINT32 Appendix C.3. Exposing Operation StatisticsAppendix C.4. Illegal Characters in Network Variable Names Appendix C.5. CirconSI LimitationsAppendix C.7. Combining Explicit and Implicit Appendix D. SNVTType Location array element Kilo-British Thermal 65,535 Units Mega-British Thermal Sender Range Lower ID Data Length Suggested Data Array Formats KiloJoules per Kilogram FS-8700-21 LonWorks Manual Data Length Suggested Data Array Formats Float Measurement Units Values Range Invalid Value 163.840 Type Raw SNVTmassf FS-8700-21 LonWorks Manual Data Item Measurement Units Values Range Invalid Value Parts per Million ppm FS-8700-21 LonWorks Manual Measurement Units Values Range Invalid Value SNVTpumpsensor SNVTpumpsetmn Measurement Units Values Range Invalid Value SNVTpumpsetmn SNVTpwrfactf RPM Millimeters per Second Difference Type Measurement Units Values Range Invalid Value SNVTtempsetpt FS-8700-21 LonWorks Manual Kiloliters kl Measurement Units Values Range Invalid Value SNVTzerospan