Appendix B.2. Neuron Systems

Newron Systems may produce the following Error message “bindings lost after power-cycle” The solution to this is to place the FieldServer in the Configured state which will cause the bindings to be committed to the Neuron and they will remain after a power cycle.

Procedure:

1)Make the bindings in NL220

2)Place devices in ONLINE mode or state.

3)Refer to the following Screencap for assistance in placing the FieldServer in the Configured state.

Appendix B.3. Honeywell Care

This system uses unacknowledged service as default. This protocol driver requires acknowledged service to operate correctly.

Appendix B.4. Tridium JACE

This system uses unacknowledged service as default. This protocol driver requires acknowledged service to operate correctly.

Note that Tridium calls Acknowledged service “critical bindings”.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

Image 31
Contents Driver Manual FS-8700-21 LonWorks Table of Contents Appendix D. SNVTType Network Management NV Updates/PollsLonWorks Program ID Calculation Spid XIF Files Configuration PropertiesClients/Servers Explicit/ImplicitProvided by the Supplier of 3 rd Party Equipment Supplied by FieldServer Technologies for this driverAdditional files required for the Driver Hardware Connections Service PinLonWorks Adapter Card FS-X40 only Port Address SwitchNeuron ID Lon LED’sSNVTIndex Special considerationsMap Descriptor Names Network Variable Names Implicit Lon functionsClient vs Server Mapping Network Management CapabilityClient Side Mapping Connection Parameters FieldServer Related Map Descriptor Parameters Node ParametersTiming Parameters Driver Related Map Descriptor ParametersClient Side Map Descriptor Example Lon functions Explicit ConfigurationsDomain Table Setup Network Management Nodes Client Side Configuration ConnectionsFS-8700-21 LonWorks ManualPage 18 Map Descriptor Example 2 Polling UNVT’s Using Neuron ID to Address Devices Client Drivers only Server Side Configuration Connections FS-8700-21 LonWorks ManualPage 22 Map Descriptor Example Appendix A.4. XIF Generation Appendix A.1. Using UNVT’sAppendix A.2. Using NVMin, NVMax etc Appendix A.3. Throttling ModeAppendix A.6. LonMark Object Creation Appendix A.5. Configuration PropertiesCfgnvui Appendix A.8. Working with Binary Data Appendix A.7. Node Status OperationAppendix A.9. Filtering Snvt Variables FS-8700-21 LonWorks Manual Appendix B.1. Echelon LonMaker Appendix B. Vendor InformationAppendix B.3. Honeywell Care Appendix B.2. Neuron SystemsAppendix B.4. Tridium Jace Appendix B.5. Trane Rover Appendix C.1. Debugging a LonWorks connection Hints and tips Appendix C.2. Error MessagesUINT32 Appendix C.3. Exposing Operation StatisticsAppendix C.5. CirconSI Limitations Appendix C.4. Illegal Characters in Network Variable NamesAppendix C.7. Combining Explicit and Implicit Appendix D. SNVTType Location array element Kilo-British Thermal 65,535 Units Mega-British Thermal Sender Range Lower ID Data Length Suggested Data Array Formats KiloJoules per Kilogram FS-8700-21 LonWorks Manual Data Length Suggested Data Array Formats Float Measurement Units Values Range Invalid Value 163.840 Type Raw SNVTmassf FS-8700-21 LonWorks Manual Data Item Measurement Units Values Range Invalid Value Parts per Million ppm FS-8700-21 LonWorks Manual Measurement Units Values Range Invalid Value SNVTpumpsensor SNVTpumpsetmn Measurement Units Values Range Invalid Value SNVTpumpsetmn SNVTpwrfactf RPM Millimeters per Second Difference Type Measurement Units Values Range Invalid Value SNVTtempsetpt FS-8700-21 LonWorks Manual Kiloliters kl Measurement Units Values Range Invalid Value SNVTzerospan