Display Low Batteries NOT IMPLEMENTED￿

Timeout Values The system has many settings or operations, which after a predetermined period of time￿ automatically cancel. This is where these values are set. Refer to the EDA-M100 manual for descriptions of￿ these values￿

Analogue Global Options Only required for analogue systems that use the analogue range of detectors. %￿ level changes when changing from day to night mode. + sets the units more sensitive, - sets the units less￿ sensitive. The pre alarm level is a % of the alarm value and should be defaulted to 95% . The head dirty is￿ a percentage of the alarm level and should be set to approximately 85%.￿

Save as Default Once the default values are set they can be saved as the defaults and loaded for the next￿ new system. To do this click ‘Save as Default’￿

Load Defaults If previously the settings have been saved as default they can be reloaded into the system￿ by clicking ‘load default’.￿

Exit and Save To return to the main screen press exit and save. Any values changed on the screen will￿ now be stored. If there are any values that are incorrect they must be corrected before exiting this screen.￿

5.7 Saving Settings to Disk￿

Once the messages and cause and effects have been completed they should be saved to disk. As a pre-￿ cautionary measure it would be worth while saving the information to the disk drive on regular occasions￿ throughout entering lots of information in case of problems with the PC. The system does not auto-save the￿ work.￿

Click on ‘Save to Disk’ and the following screen will be displayed.￿

Select the appropriate directory. Type the file name to be saved or click on the existing file if to be over writ-￿ ten and then click on the save button.￿

5.8 Sending Settings to Panel￿

When the messages and cause and effects have been programmed correctly, the information is required to￿ be downloaded into all the panels.￿

Messages and options are required to be loaded into display panels whereas only options are required to￿ be loaded into booster. This must be performed to ensure correct operation of the system. .￿

If only defaults are used (including zones) options do not require loading into panels.￿ Having clicked on the ‘Download to Panel’ button the screen as shown in figure 5.8 appears.￿ In order to download the correct information, the following parameters have to be set.￿ Messages/Options Allows the user to select whether to down load options, messages or both.￿ M100/M200 Select panel type being down loaded￿

Panel Port Select front panel port for the particular lead being used.￿ Com Port Select PC Comm port being used￿

Panel Software Select appropriate version of software￿

Status Information This details the amount of options/messages loaded￿