Page - 5 Windmill
Device Type The device type of the unit installed. To ensure correct operation this value must be correct. The codes follow the product code. If you are unsure then the ‘X’ option must be used. Zone
The zone number must be programmed between the following values
Locations Text The device location text can be set using a maximum of 37 characters
Day/Night Mode On If analogue devices are being used (500 and 600 range of detectors) then for
Sensitivity If analogue devices have been fitted *500 and 600 range of detectors) then the sensitivity can be selected. The default is ‘Normal’ but if a higher sensitivity is required for computer rooms or high risk areas the sensitivity should be set higher. If devices are fitted in hostile areas or roof voids then the lower sensitivity should be set.
2nd Input Used If the 2nd input is being used this check box must be selected to allow a unit number to be entered.
2nd Input Device Number If the 2nd input is used a device number must be assigned. This will be the
Save and Exit To return to the previous screen this button must be pressed.
Once changes are made they are automatically saved and can only be changed back by
5.4.2 Change Device Cause and Effects
If the cause and effects for a particular device need to be changed position the scroll bar to detail the
If the device number is not correct then the up and down arrows can be used to reposition the device number. It should be noted that any changes made prior to changing the device number will automatically be saved.