Johnson Controls XP-910x, XT-9100 appendix Analog Input

Page 10

Analog Input

Configuration

AI Input Type:

Measurement

Units

Note: The data base in the XT-9100 has been designed to accept most configuration of inputs and outputs. All inputs and outputs which are physically connected through expansion modules must be configured, and only those points. If there is a difference between the physical configuration and the software configuration, the XT-9100 will signal an error condition to the DX-9100 (XTnERR).

Each analog input is defined and configured by the following parameters:

Tag name (optional, GX-only)

Measurement units (for RTD inputs)

Enable square root

Alarm on unfiltered value

Input signal range

Alarm limits

Filter time constant

The GX Tool determines the input signal range with a 2-stage process: you must first decide if the input is active or passive; the remaining options depend on this choice. With the SX Tool, this information is entered into a number of Items.

Via the GX Tool

Select XTn, AIn, then either Active or Passive.

Note: All AI points must be configured even if not connected to a sensor to enable the generation of a complete IO Map and to ensure correct operation with the DX-9100 Controller.

Via the GX Tool

The selection of Celsius or Fahrenheit, is set in the Global data of the DX-9100 (select DX-9100, then Global. At the “Temperature Units” field, enter “C” for Celsius or “F” for Fahrenheit).

To determine the measurement units of active inputs, select XTn, AIn, Data, and then enter in the “Measurement Units” field:

0 = None

1 = Temperature (“C” or “F” as entered in Global)

2 = Percent (%)

Note: The units of an active input are not read by the DX-9100 Controller, but are available to any other Supervisory System which may be connected.

10Configuration Guides—XT-9100 Configuration Guide

Image 10
Contents XT-9100 Configuration Guide Configuration Guides-XT-9100 Configuration Guide XT-9100 Extension Module XP-910x Expansion Modules IntroductionHardware Configuration Model Codes XT/XP/TR Model CodesTypical XT-9100 Configuration XT Configurations Configuration Guides-XT-9100 Configuration Guide Software Configuration XT-9100 Type SettingsVia SX Tool XT-9100 Configuration Analog Input Via the GX Tool Option Only Available with Active Sensor AI Input Type Input Signal Range AI Input Type Alarm Limits Filter Time Constant AI Notes Digital Input Configuration Analog Output Configuration RI.09AO Output Type Via the GX Tool AO Source With DX-9100 Only AO Notes Digital Output Configuration Do Source With DX-9100 Only Do Notes Download/ Upload Upload via a DX-9100 Controller Appendix 1 SX Tool Item Description and Tables General Item Address Item TypeItem Tag Read/Write Data R/W Floating Point Numbers Item List MmmmmmmmmmmFail ModlOpmo PWRDOS2 DOS1DIS1 AIH1 DIS2AIS AIL1AI3 AI1AI2 AI4CNF PC3 CNF PC1CNF PC2 CNF PC4CNF DIT2 CNF DOT1CNF XTS CNF DOT2CNF Dopt CNFXP2 CNF IomapXP1 CNF IotypCNF Mtbc CNF IomodCNF AOT CNF LR1 CNF AIT1CNF HR1 HIA1CNF LR3 CNF AIT3CNF HR3 HIA3CNF LR6 CNF AIT6CNF HR6 HIA6Configuration Guides-XT-9100 Configuration Guide Configuration Guides-XT-9100 Configuration Guide Controls Group FAN