Johnson Controls XT-9100, XP-910x appendix AI Input Type Alarm Limits

Page 13

AI Input Type: Alarm Limits

Via the SX Tool

Input Type:

 

X7 = 0

0-10 volts

X7 = 1

0-20 mA

X8 = 1

20% suppression 2-10V or 4-20 mA)

Linearization and Sensor Type:

X11 X10 X9 = 000

Linear (Active Sensor)

X11 X10 X9 = 001

Ni 1000 RTD Passive Sensor (JCI Type)

 

(-45 to +121°C/-50 to +250°F)

X11 X10 X9 = 010

Ni 1000 RTD High Temperature Sensor

 

(+21 to +288°C/70 to +550°F)

X11 X10 X9 = 011

RTD Sensor A99

 

(-50 to +100°C/-58 to +212°F)

X11 X10 X9 = 100

RTD Sensor Platinum 1000

 

(+50 to +200°C/-58 to +320°F)

For active inputs, each analog input module channel performs the conversion of the input signal to a numeric value using the high range at Item HRn (RI.89, RI.97, RI.105, RI.113, RI.121, RI.129, RI.137, and RI.145) and low range at Item LRn (RI.90, RI.98, RI.106, RI.114, RI.122, RI.130, RI.138, and RI.146).

For RTD inputs, the range of the displayed value is fixed according to the type of sensor.

The high limit and the low limit define at which levels the analog input reading will generate an alarm, either for remote monitoring or for internal use within the control sequences in the DX-9100.

Note: The limits cannot be deleted. If you do not want alarms, enter limits beyond the range.

Via the GX Tool

Select XTn, AIn, then Data. At the respective field, enter the limit:

High Limit =

Low Limit =

Limit Differential =

Configuration Guides—XT-9100 Configuration Guide 13

Image 13
Contents XT-9100 Configuration Guide Configuration Guides-XT-9100 Configuration Guide Introduction XT-9100 Extension Module XP-910x Expansion ModulesXT/XP/TR Model Codes Hardware Configuration Model CodesTypical XT-9100 Configuration XT Configurations Configuration Guides-XT-9100 Configuration Guide XT-9100 Type Settings Software ConfigurationVia SX Tool XT-9100 Configuration Analog Input Via the GX Tool Option Only Available with Active Sensor AI Input Type Input Signal Range AI Input Type Alarm Limits Filter Time Constant AI Notes Digital Input Configuration RI.09 Analog Output ConfigurationAO Output Type Via the GX Tool AO Source With DX-9100 Only AO Notes Digital Output Configuration Do Source With DX-9100 Only Do Notes Download/ Upload Upload via a DX-9100 Controller General Item Address Item Type Appendix 1 SX Tool Item Description and TablesItem Tag Read/Write Data R/W Mmmmmmmmmmm Floating Point Numbers Item ListOpmo ModlFail PWRDOS2 DOS1DIS1 AIS DIS2AIH1 AIL1AI2 AI1AI3 AI4CNF PC2 CNF PC1CNF PC3 CNF PC4CNF DOT1 CNF DIT2CNF Dopt CNF DOT2CNF XTS CNFXP1 CNF IomapXP2 CNF IotypCNF Mtbc CNF IomodCNF AOT CNF HR1 CNF AIT1CNF LR1 HIA1CNF HR3 CNF AIT3CNF LR3 HIA3CNF HR6 CNF AIT6CNF LR6 HIA6Configuration Guides-XT-9100 Configuration Guide Configuration Guides-XT-9100 Configuration Guide Controls Group FAN