Johnson Controls XP-910x, XT-9100 appendix Upload via a DX-9100 Controller

Page 22

Upload via a DX-9100 Controller

Only complete DX-9100/XT-9100 configurations should be uploaded from the DX-9100. Select DX-9100 and NEW to clear the PC screen. Select DX-9100, UPLOAD, and DX&XT. Enter the DX-9100 Controller address (0-255) and PC port (1 or 2). Press <Enter>.

Download via the N2 Bus

Set the address switches and jumpers on the XT/XP devices as required. Connect the XT/XP devices to the N2 Bus and the N2 Bus to the converter on the PC. (See the XT-9100 Technical Bulletin (LIT-6364040)for connection details.)

If the XT/XP devices are installed and wired, verify all field wiring and sensor voltage/current signals. It is recommended that controlled devices be isolated during download and initial startup. Apply 24 VAC power to the XT/XP devices.

Up to eight XT-9100s may be downloaded at one time from the GX Tool over the N2 Bus.

If the XT/XP devices are not used with a DX-9100, it is recommended that one configuration file is created for each XT-9100 in Position XT1.

Set the address switches and jumpers on the XT/XP devices as required. Connect the XT/XP devices to the N2 Bus and the N2 Bus to the converter on the PC. (See the XT-9100 Technical Bulletin (LIT-6364040)for details.)

If the XT/XP devices are installed and wired, verify all field wiring and sensor voltage/current signals. It is recommended that controlled devices be isolated during download and initial startup. Apply 24 VAC power to the XT/XP devices.

Up to eight XT-9100s may be downloaded at one time from the GX Tool over the N2 Bus.

If the XT/XP devices are not used with a DX-9100, it is recommended that one configuration file is created for each XT-9100 in Position XT1.

Select DX-9100, DOWNLD, and XT. Enter the PC serial communication port (1 or 2) in the “PC Port” field and press <Enter>.

Upload via the N2 Bus

Only one XT-9100 may be uploaded at one time and the configuration will be stored under XT1. Select DX-9100, UPLOAD, and XT. Enter the XT-9100 address (1-255) in the “Controller Address” field and the PC serial communication point (1, 2) in the “PC Port” field. Press <Enter>.

Via the SX Tool XT-9100 configuration data can only be changed item by item with the SX Tool. It is not possible to download or upload a complete configuration.

22Configuration Guides—XT-9100 Configuration Guide

Image 22
Contents XT-9100 Configuration Guide Configuration Guides-XT-9100 Configuration Guide XT-9100 Extension Module XP-910x Expansion Modules IntroductionHardware Configuration Model Codes XT/XP/TR Model CodesTypical XT-9100 Configuration XT Configurations Configuration Guides-XT-9100 Configuration Guide Software Configuration XT-9100 Type SettingsVia SX Tool XT-9100 Configuration Analog Input Via the GX Tool Option Only Available with Active Sensor AI Input Type Input Signal Range AI Input Type Alarm Limits Filter Time Constant AI Notes Digital Input Configuration Analog Output Configuration RI.09AO Output Type Via the GX Tool AO Source With DX-9100 Only AO Notes Digital Output Configuration Do Source With DX-9100 Only Do Notes Download/ Upload Upload via a DX-9100 Controller Appendix 1 SX Tool Item Description and Tables General Item Address Item TypeItem Tag Read/Write Data R/W Floating Point Numbers Item List MmmmmmmmmmmFail ModlOpmo PWRDOS2 DOS1DIS1 AIH1 DIS2AIS AIL1AI3 AI1AI2 AI4CNF PC3 CNF PC1CNF PC2 CNF PC4CNF DIT2 CNF DOT1CNF XTS CNF DOT2CNF Dopt CNFXP2 CNF IomapXP1 CNF IotypCNF Mtbc CNF IomodCNF AOT CNF LR1 CNF AIT1CNF HR1 HIA1CNF LR3 CNF AIT3CNF HR3 HIA3CNF LR6 CNF AIT6CNF HR6 HIA6Configuration Guides-XT-9100 Configuration Guide Configuration Guides-XT-9100 Configuration Guide Controls Group FAN