Digital Output Configuration
DO: Type of Output
DO: Pulse Time
Each digital output is defined and configured by the following parameters:
∙Tag name
∙Output type
∙Pulse time
When the XT is connected to a
∙Source
Via the GX Tool
Select XTn (or EXP) and DOn, then select either of the On/Off or Pulse fields. For the Pulse type, the output switches for a configurable pulse time for each state transition of the command output.
Via the SX Tool
The output type for outputs
X1 = 0 On/Off Type (Maintained)
X1 = 1 Pulse Type; the output switches for a configurable pulse time for each state transition of the command output
This parameter is set once for all pulse type outputs in the
Via the GX Tool
Select XTn, XTn, and Data, then enter a value in the “Digital Output Pulse Time” field. The valid range is 1 to 250 (5 msec to 1.25 seconds pulse time).
Via the SX Tool
The digital output pulse time can be defined in Item DOPT (RI.68) in units of 5 msec. The default value is 200, which represents a pulse time of
1 second.
Note: All connected DO points must be configured to ensure correct operation with the