Johnson Controls XP-910x, XT-9100 appendix Via SX Tool

Page 8

Maximum Time

Between

Communications

Operational Mode (SX Only)

XT Address

Via the SX Tool

The “Output Hold/Reset on Communication Failure” flag is set at Bit X2 of Item XTS (RI.69).

X2 = 0 Output reset upon communication failure

X2 = 1 Output hold upon communication failure

When communication fails for the period set in this Item, the XT-9100 goes into “communication failure” state, indicated by a blinking power LED on the front of the module. The default value is 60 seconds.

Via the GX Tool

First configure an XT Module. Select XTn, then Analog or Digital. Then select the just configured XTn, XTn, and Data. At the “Comm. timeout (sec)” field, enter the value in seconds.

Via the SX Tool

The “Maximum Time Between Communications” (in seconds) is entered at Item MTBC (RI.86).

The operational mode of the XT-9100 can be seen at Item OPMO (RI.01) with following status bits:

X8 = 1 PWR Power Failure. This bit is set when a XT is powered up or when there is a serial interface communication failure.

The setting in Item XTS (RI.69) Bit X2 (“Output Hold/Reset on Communication Failure” flag) is repeated in Item OPMO (RI.01) Bit X7 so that it can be read by the DX-9100 or any other monitoring system.

Via the GX Tool

In order to download the XT-9100 devices it is necessary to enter the XT addresses. These addresses will also be loaded into the DX-9100. When performing a download through a DX-9100 Controller, the controller only downloads the addresses of its own XT set. The

XT address is not stored in the XT-9100 but must be set on the address switches on the module.

First configure an XT Module. Select XTn, then Analog or Digital. Then select the just configured XTn, XTn, and Data. At the “Hardware Address” field, enter the address (1-255) of the XT-9100 module.

Via SX Tool

Refer to the Extension Module Configuration section in the DX-9100 Configuration Guide (LIT-6364030).

8Configuration Guides—XT-9100 Configuration Guide

Image 8
Contents XT-9100 Configuration Guide Configuration Guides-XT-9100 Configuration Guide XT-9100 Extension Module XP-910x Expansion Modules IntroductionHardware Configuration Model Codes XT/XP/TR Model CodesTypical XT-9100 Configuration XT Configurations Configuration Guides-XT-9100 Configuration Guide Software Configuration XT-9100 Type SettingsVia SX Tool XT-9100 Configuration Analog Input Via the GX Tool Option Only Available with Active Sensor AI Input Type Input Signal Range AI Input Type Alarm Limits Filter Time Constant AI Notes Digital Input Configuration Analog Output Configuration RI.09AO Output Type Via the GX Tool AO Source With DX-9100 Only AO Notes Digital Output Configuration Do Source With DX-9100 Only Do Notes Download/ Upload Upload via a DX-9100 Controller Appendix 1 SX Tool Item Description and Tables General Item Address Item TypeItem Tag Read/Write Data R/W Floating Point Numbers Item List MmmmmmmmmmmModl OpmoFail PWRDIS1 DOS1DOS2 DIS2 AISAIH1 AIL1AI1 AI2AI3 AI4CNF PC1 CNF PC2CNF PC3 CNF PC4CNF DIT2 CNF DOT1CNF DOT2 CNF DoptCNF XTS CNFCNF Iomap XP1XP2 CNF IotypCNF AOT CNF IomodCNF Mtbc CNF AIT1 CNF HR1CNF LR1 HIA1CNF AIT3 CNF HR3CNF LR3 HIA3CNF AIT6 CNF HR6CNF LR6 HIA6Configuration Guides-XT-9100 Configuration Guide Configuration Guides-XT-9100 Configuration Guide Controls Group FAN