Johnson Controls XP-910x appendix XT-9100 Configuration

Page 9

XT-9100 Configuration

Settings

Via the GX Tool

The I/O type and map details are automatically generated by the GX-9100 Graphic Configuration Software when all I/O data for extension modules has been entered. It is then downloaded into the XT-9100 directly or via the DX-9100 and XT-Bus. (Refer to the Download/Upload section, further in this document.)

When in the GX Tool, select the XT module, then define it as Analog or Digital (if Digital, define it as 8 DI, 4DI/4DO, or 8DO). This defines Module XP1. If an XT has 16 points (XP2 is connected), select the XT box immediately to the right of the configured module, select EXP.DIG and define it as 8DI, 4DI/4DO, or 8DO. “EXP” will appear in the XT box. Then select XT (or EXP) again and define each point in the selected configuration in the same way as when defining the points in the DX-9100. The following pages describe how to define each of the points individually.

Via the SX Tool

Each extension module configuration is defined by the I/O types and map which are configured in Extension Module Items IOMAP (RI.77), IOTYP (RI.78), and IOMOD (RI.79).

1.The I/O map (IOMAP) defines which inputs/outputs (in pairs) on the extension module are used. Each extension module can be defined with eight used points, which normally reside in the XP1 (first) Expansion Module (points I/O1-I/O8), defined in bits X1-X4.

When an extension module has an XP2 (second) Expansion Module with a further eight points, these points must be defined in bits X5-X8.

2.The I/O type (IOTYP) defines which inputs/outputs (in pairs) are analog and which are digital. As the points on XP2 (if used) must be digital, only bits X1-X4 can be configured.

3.The I/O mode (IOMOD) defines points as “input” or “output”

(in pairs). Only those points declared as “used” in Item IOMAP will be monitored or controlled.

The combination of data in the Items IOMAP, IOTYP, and IOMOD completely defines the configuration of an extension module. When connected to a DX-9100 Controller, an identical set of data must be entered into the Item data base in the DX-9100 Controller, so that, when the DX-9100 and XT-9100 are connected and started up, the DX-9100 will compare data bases and only send commands to the extension module if the data is identical, thus avoiding incorrect control actions.

Configuration Guides—XT-9100 Configuration Guide 9

Image 9
Contents XT-9100 Configuration Guide Configuration Guides-XT-9100 Configuration Guide Introduction XT-9100 Extension Module XP-910x Expansion ModulesXT/XP/TR Model Codes Hardware Configuration Model CodesTypical XT-9100 Configuration XT Configurations Configuration Guides-XT-9100 Configuration Guide XT-9100 Type Settings Software ConfigurationVia SX Tool XT-9100 Configuration Analog Input Via the GX Tool Option Only Available with Active Sensor AI Input Type Input Signal Range AI Input Type Alarm Limits Filter Time Constant AI Notes Digital Input Configuration RI.09 Analog Output ConfigurationAO Output Type Via the GX Tool AO Source With DX-9100 Only AO Notes Digital Output Configuration Do Source With DX-9100 Only Do Notes Download/ Upload Upload via a DX-9100 Controller General Item Address Item Type Appendix 1 SX Tool Item Description and TablesItem Tag Read/Write Data R/W Mmmmmmmmmmm Floating Point Numbers Item ListOpmo ModlFail PWRDOS1 DOS2DIS1 AIS DIS2AIH1 AIL1AI2 AI1AI3 AI4CNF PC2 CNF PC1CNF PC3 CNF PC4CNF DOT1 CNF DIT2CNF Dopt CNF DOT2CNF XTS CNFXP1 CNF IomapXP2 CNF IotypCNF Iomod CNF MtbcCNF AOT CNF HR1 CNF AIT1CNF LR1 HIA1CNF HR3 CNF AIT3CNF LR3 HIA3CNF HR6 CNF AIT6CNF LR6 HIA6Configuration Guides-XT-9100 Configuration Guide Configuration Guides-XT-9100 Configuration Guide Controls Group FAN