Johnson Controls XP-910x appendix Software Configuration, XT-9100 Type Settings

Page 7

XT-9100 Type Settings

Power Line Frequency (50 or 60 Hz)

Output Hold/Reset on Comm. Failure Flag

Software Configuration

Software configuration involves the setting of all the Items of the extension module to values which correspond to the intended application. Typically, use the GX Tool to configure a system, and the SX Tool to troubleshoot. To use these tools, refer to the GX-9100 Software Configuration Tool for Windows User’s Guide (LIT-6364060)and the SX-9100 Service Module User’s Guide (LIT-6364070) . Proceed in the following order:

1.Define XT-9100 type settings.

2.Define XT-9100 configuration.

3.Define analog input characteristics.

4.Define digital input characteristics.

5.Define analog output characteristics.

6.Define digital output characteristics.

Via the GX Tool

Select DX-9100 and then Global. Enter the frequency as 50 or 60. The XT frequency and the DX frequency are both defined here.

Via the SX Tool

Set Bit X1 of Item XTS (RI.69).

X1 = 0 50 Hz power line

X1 = 1 60 Hz power line

Via the GX Tool

First configure an XT Module. Select XTn, then Analog or Digital. Then select the just configured XTn, XTn, and Data.

To set this flag, at the “Status on comm. fail” (communication failure) field, enter 0 or 1.

When this bit is set to “0,” the digital outputs are switched off upon a serial interface failure, and the corresponding Item values are reset to zero.

When set to “1,” the digital outputs hold their current state upon a serial interface failure.

Configuration Guides—XT-9100 Configuration Guide 7

Image 7
Contents XT-9100 Configuration Guide Configuration Guides-XT-9100 Configuration Guide Introduction XT-9100 Extension Module XP-910x Expansion ModulesXT/XP/TR Model Codes Hardware Configuration Model CodesTypical XT-9100 Configuration XT Configurations Configuration Guides-XT-9100 Configuration Guide XT-9100 Type Settings Software ConfigurationVia SX Tool XT-9100 Configuration Analog Input Via the GX Tool Option Only Available with Active Sensor AI Input Type Input Signal Range AI Input Type Alarm Limits Filter Time Constant AI Notes Digital Input Configuration RI.09 Analog Output ConfigurationAO Output Type Via the GX Tool AO Source With DX-9100 Only AO Notes Digital Output Configuration Do Source With DX-9100 Only Do Notes Download/ Upload Upload via a DX-9100 Controller General Item Address Item Type Appendix 1 SX Tool Item Description and TablesItem Tag Read/Write Data R/W Mmmmmmmmmmm Floating Point Numbers Item ListPWR ModlOpmo FailDOS2 DOS1DIS1 AIL1 DIS2AIS AIH1AI4 AI1AI2 AI3CNF PC4 CNF PC1CNF PC2 CNF PC3CNF DOT1 CNF DIT2CNF CNF DOT2CNF Dopt CNF XTSCNF Iotyp CNF IomapXP1 XP2CNF Mtbc CNF IomodCNF AOT HIA1 CNF AIT1CNF HR1 CNF LR1HIA3 CNF AIT3CNF HR3 CNF LR3HIA6 CNF AIT6CNF HR6 CNF LR6Configuration Guides-XT-9100 Configuration Guide Configuration Guides-XT-9100 Configuration Guide Controls Group FAN