Johnson Controls XT-9100 CNF AIT1, CNF HR1, CNF LR1, HIA1, LOA1, ADF1, CNF FTC1, CNF AIT2, HIA2

Page 35

RI.

HI.

Type

R/W

Tag

Description

88

58

2 Bytes

CNF

 

AIT1

Input Type of Analog Input 1

 

 

0 0 0 0

0 X11

X10

X9

Unit of Measure

 

 

X8 X7 X6 X5 X4 X3

X2

X1

 

 

 

X4 X3 X2 X1

 

 

 

 

 

 

= 0000

 

 

 

No Units

 

 

= 0001

 

 

 

Degrees Celsius or Kelvin

 

 

= 0010

 

 

 

Degrees Fahrenheit

 

 

= 0011

 

 

 

Percent

 

 

X5 = 1

 

 

 

Enable Square Root of Input

 

 

X6 = 1

 

 

 

Alarm on Unfiltered Value

 

 

X7 = 0

 

 

 

0-10 Volts

 

 

X7 = 1

 

 

 

0-2 Volts, 0-20 mA or RTD

 

 

X8 = 1

 

 

 

20 % Suppression

 

 

X11 X10 X9

 

 

Linearization and Sensor Type

 

 

= 000

 

 

 

Linear (active sensor)

 

 

= 001

 

 

 

Nickel 1000 (JCI)

 

 

= 010

 

 

 

Nickel 1000 Ext. Rng

 

 

= 011

 

 

 

A99 Sensor

 

 

= 100

 

 

 

PT1000 Sensor

89

59

Number

CNF

 

HR1

High Range Analog Input 1

90

5A

Number

CNF

 

LR1

Low Range Analog Input 1

91

5B

Number

R/W (E)

 

HIA1

High Alarm Limit Analog Input 1

92

5C

Number

R/W (E)

 

LOA1

Low Alarm Limit Analog Input

93

5D

Number

R/W (E)

 

ADF1

Differential on Alarm Limit [units]

94

5E

Number

CNF

 

FTC1

Filter Constant Analog Input 1

95

5F

2 Bytes

 

 

 

Spare

96

60

2 Bytes

CNF

 

AIT2

Input Type of Analog Input 2 (bits

 

 

 

 

 

 

as AIT1)

97

61

Number

CNF

 

HR2

High Range Analog Input 2

98

62

Number

CNF

 

LR2

Low Range Analog Input 2

99

63

Number

R/W (E)

 

HIA2

High Alarm Limit Analog Input 2

100

64

Number

R/W (E)

 

LOA2

Low Alarm Limit Analog Input 2

101

65

Number

R/W (E)

 

ADF2

Differential on Alarm Limit [units]

102

66

Number

CNF

 

FTC2

Filter Constant Analog Input 2

103

67

2 Bytes

 

 

 

Spare

Configuration Guides—XT-9100 Configuration Guide 35

Image 35
Contents XT-9100 Configuration Guide Configuration Guides-XT-9100 Configuration Guide Introduction XT-9100 Extension Module XP-910x Expansion ModulesXT/XP/TR Model Codes Hardware Configuration Model CodesTypical XT-9100 Configuration XT Configurations Configuration Guides-XT-9100 Configuration Guide XT-9100 Type Settings Software ConfigurationVia SX Tool XT-9100 Configuration Analog Input Via the GX Tool Option Only Available with Active Sensor AI Input Type Input Signal Range AI Input Type Alarm Limits Filter Time Constant AI Notes Digital Input Configuration RI.09 Analog Output ConfigurationAO Output Type Via the GX Tool AO Source With DX-9100 Only AO Notes Digital Output Configuration Do Source With DX-9100 Only Do Notes Download/ Upload Upload via a DX-9100 Controller General Item Address Item Type Appendix 1 SX Tool Item Description and TablesItem Tag Read/Write Data R/W Mmmmmmmmmmm Floating Point Numbers Item ListPWR ModlOpmo FailDIS1 DOS1DOS2 AIL1 DIS2AIS AIH1AI4 AI1AI2 AI3CNF PC4 CNF PC1CNF PC2 CNF PC3CNF DOT1 CNF DIT2CNF CNF DOT2CNF Dopt CNF XTSCNF Iotyp CNF IomapXP1 XP2CNF AOT CNF IomodCNF Mtbc HIA1 CNF AIT1CNF HR1 CNF LR1HIA3 CNF AIT3CNF HR3 CNF LR3HIA6 CNF AIT6CNF HR6 CNF LR6Configuration Guides-XT-9100 Configuration Guide Configuration Guides-XT-9100 Configuration Guide Controls Group FAN