NOTE: The MCP 5000iE and 7000iE's AC input must be connected to an AC circut breaker which will provide for an emergency power off. (Must be performed by Authorized

Service Personnel ONLY)

Model

MCP 5000iE

MCP7000iE

Input Circuit Breaker

40 Amp

50 Amp

Input Wire Size/Temp

8 AWG/min75°C

6 AWG/min75°C

Wire Conductor

Three conductor, copper wire only

Tightening torque for

Torque 17.6Lbs (8kg)

pressure wire connectors

having screws

 

 

Block diagram of the MCP 5000iE and MCP 7000iE input and output wiring.

English

9

Image 10
Contents MCP-E Series Table of Contents Important Safety Instructions IntroductionPara Systems Life Support Policy Controls and Indicators Front Panel LCD UnitsEnglish Installation Installation PlacementMCP 5000iE and MCP 7000iE Installation Service Personnel only Installation of the mounting tray and the stablizing feet English Computer Interface Connection Optional Connecting to AN AC SourceConnecting Your Equipment Network Surge Protection Connection OptionalOperation Turning the Unit ON/OFFEnglish Alarms On BatteryEnglish Troubleshooting Diagnostic codes for 700VA and 1KVAEnglish Diagnostic Error Codes for 2KVA, 3KVA, 5KVA, 7KVA units Replacing the Battery Replacing the BatteryCSB Battery Replacement Procedure for Tower Model Battery Replacement Procedure for Rack Mount Models Obtaining Service If the UPS Requires ServiceSpecifications Input Non-Battery OperationConfigurable Parameters and Settings Function Factory Default User Choices DescriptionCustomized Output Receptacle Panels Limited Product Warranty Limited Product WarrantyDeclaration of Conformity 302