Battery Replacement Procedure for Rack Mount Models

(Must be performed by Authorized Service Personnel ONLY)

PLEASE READ THE CAUTIONS BEFORE ATTEMPTING TO REPLACE THE BATTERIES These units are hot-swappable.Hot-swappable batteries means that the batteries can be replaced without powering down the whole UPS system. NOTE: If there is a power interruption while replacing the hot-swappable batteries, with the UPS on, the load will not be backed up.

1.Utitlize steps 1-5 from page 22 if you do not want to hot-swap. Then proceed.

2.Remove the three retaining screws from front panel of the UPS.

3.Remove the six retaining screws and the battery case retaining bracket.

4.Disconnect the battery wiring harness connector.

5.Remove the battery case.

6.Insert the new battery case.

7.Connect the battery harness connnector.

8.Reinstall the battery case retaining bracket and the retaining screws.

9.Reinstall the front panel and the retaining screws.

10.Dispose of the batteries properly at an appropriate recycling facility or return them to the supplier in the packing material for the new batteries. Follow local EPA guidelines when disposing of batteries. Note: These batteries contain lead and must be disposed of per environmental guidelines.

11.The UPS is now ready for the normal start-up procedure if required.

English

23

Image 24
Contents MCP-E Series Table of Contents Important Safety Instructions IntroductionPara Systems Life Support Policy Controls and Indicators Front Panel LCD UnitsEnglish Installation Installation PlacementMCP 5000iE and MCP 7000iE Installation Service Personnel only Installation of the mounting tray and the stablizing feet English Connecting to AN AC Source Connecting Your EquipmentComputer Interface Connection Optional Network Surge Protection Connection OptionalOperation Turning the Unit ON/OFFEnglish Alarms On BatteryEnglish Troubleshooting Diagnostic codes for 700VA and 1KVAEnglish Diagnostic Error Codes for 2KVA, 3KVA, 5KVA, 7KVA units Replacing the Battery Replacing the BatteryCSB Battery Replacement Procedure for Tower Model Battery Replacement Procedure for Rack Mount Models Obtaining Service If the UPS Requires ServiceSpecifications Input Non-Battery OperationConfigurable Parameters and Settings Function Factory Default User Choices DescriptionCustomized Output Receptacle Panels Limited Product Warranty Limited Product WarrantyDeclaration of Conformity 302