Minuteman UPS MCP-E user manual Battery Replacement Procedure for Tower Model

Page 23

English

Battery Replacement Procedure for Tower Model

(Must be performed by Authorized Service Personnel ONLY)

PLEASE READ THE CAUTIONS BEFORE ATTEMPTING TO REPLACE THE BATTERIES These units are not hot-swappable.Hot-swappable batteries means that the batteries can be replaced without powering down the whole UPS system.

1.Turn off the equipment that is plugged into the output receptacles of the UPS.

2.Turn off the UPS using the primary power switch on the front.

3.Turn off the AC circuit breaker on the rear panel of the UPS (if applicable).

4.Unplug the UPS's AC power cord from the AC outlet.

5.Unplug the equipment from the output receptacles of the UPS.

6.Remove the cover of the UPS.

7.Disconnect the battery positive (red) wire and the all of the battery jumper wires.

8.Disconnect the battery negative (black) wire.

9.Remove the top four retaining screws and the top battery retaining bracket.

Step 7

Step 9

Step 8

10.Remove the top row of the batteries.

11.Remove the bottom four retaining screws and the bottom battery retaining bracket.

12.Remove the bottom row of the batteries.

13.Install the bottom row of new batteries.

14.Reinstall the bottom battery retaining bracket and the retaining screws.

15.Install the top row of new batteries.

16.Reinstall the top battery retaining bracket and the retaining screws.

17.Reconnect the battery negative (black) wire and the battery jumper wires. Verify proper polarity, negative (black) wire to the battery negative terminal and the battery jumper wires are connected properly.

18.Reconnect the battery positive (red) wire to the battery positive terminal. Some sparking may occur, this is normal.

19.Reinstall the cover on the UPS.

20.Dispose of the batteries properly at an appropriate recycling facility or return them to the supplier in the packing material for the new batteries. Follow local EPA guidelines when disposing of batteries. Note: These batteries contain lead and must be disposed of per environmental guidelines.

21.The UPS is now ready for the normal start-up procedure.

22

Image 23
Contents MCP-E Series Table of Contents Introduction Important Safety InstructionsPara Systems Life Support Policy Front Panel LCD Units Controls and IndicatorsEnglish Installation Placement InstallationMCP 5000iE and MCP 7000iE Installation Service Personnel only Installation of the mounting tray and the stablizing feet English Network Surge Protection Connection Optional Connecting to AN AC SourceConnecting Your Equipment Computer Interface Connection OptionalTurning the Unit ON/OFF OperationEnglish On Battery AlarmsEnglish Diagnostic codes for 700VA and 1KVA TroubleshootingEnglish Diagnostic Error Codes for 2KVA, 3KVA, 5KVA, 7KVA units Replacing the Battery Replacing the BatteryCSB Battery Replacement Procedure for Tower Model Battery Replacement Procedure for Rack Mount Models If the UPS Requires Service Obtaining ServiceInput Non-Battery Operation SpecificationsFunction Factory Default User Choices Description Configurable Parameters and SettingsCustomized Output Receptacle Panels Limited Product Warranty Limited Product WarrantyDeclaration of Conformity 302