Communications port information for 2KVA, 3KVA, 5KVA and 7KVA units only:

These units contain two independent communications ports. Port one is for standard RS232 communications and labeled RS-232 Port. The second port is relay contact closure configured for standard AS 400 ports. This port is labeled Control Port.

The pinout for the RS-232 port is depicted per the chart below. Note: when using the SNMP option card, this port will be disconnected. Both the slot and the port may not be used at the same time.

Communication settings: When using the RS232 port, the following settings should be used.

Baud Rate: 2400

Data Bits: 8

Stop Bits: None

Parity: 1

Pin 1:

Not Used

Pin 2:

/TXD Transmit Data

Pin 3:

/RXD Receive Data and Commands

Pin 4:

Not Used

Pin 5:

Ground

Pin 6:

Not Used

Pin 7:

Not Used

Pin 8:

Not Used

Pin 9:

Not Used

The pinout for the Control port is depicted per the chart below.

Pin 1: UPS failure (fault)

Pin 2: Summary alarm (normally open, closes on event)

Pin 3: Common for pin 4

Pin 4: EPO or shutdown

Pin 5: Common ground for all relays.

Pin 6: Bypass active=make/ ups on=open

Pin 7: Battery low (normally open, closes on event)

Pin 8: UPS on=make/ bypass active=open

Pin 9: AC fail (normally open, closes on event)

Your UPS unit is shipped standard with SentryII monitoring software. This software may be used for monitoring the UPS and power when loaded into your computer and connected via the supplied software communication cable. This software is a detailed tool to help you manage your power needs.

This software will also support a simpler style of controlled shutdown for the consumer that is not interested in detail, but is still interested in a controlled unattended shutdown. The simple software function requires the purchase and installation of a separate cable that is not provided with the unit. Please contact your local vendor or Minuteman Technical support department at 800-238-7272 or 972-446-7363 should you need to purchase this software cable.

16

Image 17
Contents MCP-E Series Table of Contents Introduction Important Safety InstructionsPara Systems Life Support Policy Front Panel LCD Units Controls and IndicatorsEnglish Installation Placement InstallationMCP 5000iE and MCP 7000iE Installation Service Personnel only Installation of the mounting tray and the stablizing feet English Connecting Your Equipment Connecting to AN AC SourceComputer Interface Connection Optional Network Surge Protection Connection OptionalTurning the Unit ON/OFF OperationEnglish On Battery AlarmsEnglish Diagnostic codes for 700VA and 1KVA TroubleshootingEnglish Diagnostic Error Codes for 2KVA, 3KVA, 5KVA, 7KVA units Replacing the Battery Replacing the BatteryCSB Battery Replacement Procedure for Tower Model Battery Replacement Procedure for Rack Mount Models If the UPS Requires Service Obtaining ServiceInput Non-Battery Operation SpecificationsFunction Factory Default User Choices Description Configurable Parameters and SettingsCustomized Output Receptacle Panels Limited Product Warranty Limited Product WarrantyDeclaration of Conformity 302