INSTALLATION
(Must be performed by Authorized Service Personnel ONLY)
Be sure to read the installation placement and all the cautions before installing the UPS. The
MCP 5000iE and MCP 7000iE Input/Output/Battery Pack Connections
(Must be performed by Authorized Service Personnel ONLY)
Installation instructions for hardwiring the Input/Output Connections:
1.Crimp M6 ring terminals (part number
14or equivalent). Ring Terminal:
Size: M6 (or equivalent)
Part Number:
Manufacturer: Kai Suh Suh Enterprise Company., LTD (or equivalent) Crimp tool:
Part number: Crimpers
Manufacturer: Kai Suh Suh Enterprise Company., LTD (or equivalent)
2.Remove the access panel on the rear panel of the UPS.
3.Install the appropriate size strain relief into the input and output access holes.
4.Push the input cable through the strain relief nearest the input terminal block.
5.Connect L1 to the AC Input's "L" terminal, connect L2 to theAC Input's "N" terminal, connect AC ground to the AC Input's ground terminal. Be sure that all the connections and the strain relief are tightly secured.
6.Push the output cable through the strain relief nearest the output terminal block.
7.Connect L1 to the AC Output's "L" terminal, connect L2 to the AC Output's "N" terminal, connect AC ground to the AC Output's ground terminal. Be sure that all the connections and the strain relief are tightly secured.
8.Reinstall the access panel on the rear panel of the UPS.
9.Now the UPS is ready for the normal