Minuteman UPS MCP-E user manual Installation

Page 9

English

INSTALLATION

(Must be performed by Authorized Service Personnel ONLY)

Be sure to read the installation placement and all the cautions before installing the UPS. The MCP-E series UPS has external Battery Pack capability, please observe the following warning when connecting the Battery Pack(s). WARNING! DO NOT PLUG THE BATTERY PACK'S CONNECTOR INTO THE UPS's BATTERY CONNECTOR WHILE THE UPS IS TURNED ON. NOTE: The red connectors/wires are the battery positive(+) and the black connectors/ wires are the battery negative(-) on all MINUTEMAN configurations.

MCP 5000iE and MCP 7000iE Input/Output/Battery Pack Connections

(Must be performed by Authorized Service Personnel ONLY)

Installation instructions for hardwiring the Input/Output Connections:

1.Crimp M6 ring terminals (part number R14-6 or equivalent) to the appropriate size input and output cables (see page 9) using the appropiate Crimp tool (part number Crimpers RYO-

14or equivalent). Ring Terminal:

Size: M6 (or equivalent)

Part Number: R14-6 (or equivalent)

Manufacturer: Kai Suh Suh Enterprise Company., LTD (or equivalent) Crimp tool:

Part number: Crimpers RYO-14 (or equivalent)

Manufacturer: Kai Suh Suh Enterprise Company., LTD (or equivalent)

2.Remove the access panel on the rear panel of the UPS.

3.Install the appropriate size strain relief into the input and output access holes.

4.Push the input cable through the strain relief nearest the input terminal block.

5.Connect L1 to the AC Input's "L" terminal, connect L2 to theAC Input's "N" terminal, connect AC ground to the AC Input's ground terminal. Be sure that all the connections and the strain relief are tightly secured.

6.Push the output cable through the strain relief nearest the output terminal block.

7.Connect L1 to the AC Output's "L" terminal, connect L2 to the AC Output's "N" terminal, connect AC ground to the AC Output's ground terminal. Be sure that all the connections and the strain relief are tightly secured.

8.Reinstall the access panel on the rear panel of the UPS.

9.Now the UPS is ready for the normal start-up procedure.

8

Image 9
Contents MCP-E Series Table of Contents Introduction Important Safety InstructionsPara Systems Life Support Policy Front Panel LCD Units Controls and IndicatorsEnglish Installation Placement InstallationMCP 5000iE and MCP 7000iE Installation Service Personnel only Installation of the mounting tray and the stablizing feet English Connecting Your Equipment Connecting to AN AC SourceComputer Interface Connection Optional Network Surge Protection Connection OptionalTurning the Unit ON/OFF OperationEnglish On Battery AlarmsEnglish Diagnostic codes for 700VA and 1KVA TroubleshootingEnglish Diagnostic Error Codes for 2KVA, 3KVA, 5KVA, 7KVA units Replacing the Battery Replacing the BatteryCSB Battery Replacement Procedure for Tower Model Battery Replacement Procedure for Rack Mount Models If the UPS Requires Service Obtaining ServiceInput Non-Battery Operation SpecificationsFunction Factory Default User Choices Description Configurable Parameters and SettingsCustomized Output Receptacle Panels Limited Product Warranty Limited Product WarrantyDeclaration of Conformity 302