Nortel Networks 8010co manual Connecting cables to the chassis power supplies

Page 38

38Chapter 2 Installation

Connecting cables to the chassis power supplies

This section describes how to connect the BIP power cables to the 8010co chassis 8004DC power supplies. These procedures assume that all required power supplies were previously installed during the 8010co chassis installation.

Note: This guide does not describe how to remove or replace power supplies in the 8010co chassis. For detailed instructions about adding power supplies or modifying an existing configuration, see the appropriate product chassis installation manual.

Before beginning the procedures in this section, note the following:

A 8010co chassis configuration can consist of one or two chassis in a single rack. If a single chassis is installed, it is always installed in the lower shelf position.

Note: For a single chassis installation, always install the chassis in the lower shelf position to stabilize the rack.

Each chassis can be configured with up to three power supplies. The cabling for each power supply comprises three conductors: the positive lead wire, the negative lead wire, and the ground lead.

To access the power supplies, you may have to remove the bottom front bezel from both the upper shelf and lower shelf 8010co chassis.

Warning: Ensure that the DC power source is off or disconnected at the remote end before you perform any of the steps in this section. You may need to switch a circuit breaker off or turn off power at the DC input source. Be sure that the DC input source power is locked out and tagged.

Note: The 321325-A bezel does not need to be removed to access the power supplies.

312755-G Rev 00

Image 38
Contents Part No -G Rev May Great America Parkway Santa Clara, CA Statement of conditions Copyright 2006 Nortel Networks. All Rights ReservedTrademarks International regulatory statements of conformityCE marking statement Europe only Vcci statement Japan/Nippon onlyNortel Inc. software license agreement EN 60 950 statementGeneral Rev Contents Contents RevIndex Contents Rev Figures Rack grounding strip example Tables Tables Rev Preface Before you beginGetting Help from the Nortel Web site How to get HelpText conventions PrefaceGetting Help over the phone from a Nortel Solutions Center Getting Help through a Nortel distributor or resellerPreface Rev Chapter Overview Physical descriptionOverview Front panelShelf circuit breakers upper and lower shelves Shelf circuit breakers Alarm module display panel Alarm module display LEDsMajor Front panel locking screws Shelf alarm connectors upper and lower shelvesBack panel Shelf alarm connections upper and lower shelves Central office alarms Configuring multiple BIPs to aggregate office alarmsPower terminal block Configuring standalone BIPs to report alarm status1 3 2 1 3 2 1 a 1 a 2 B 1 B Power and grounding example Accessing the alarm module Opening the front panelAccessing the alarm module Configuration example 8010co chassis configuration with BIP optionChapter Installation Preparing to install the breaker interface panelShipment contents Mounting hardware DC power requirementsAdditional equipment DC input electrical requirementsInstalling the breaker interface panel Installing the hardwareRemoving the plastic back cover from the BIP Connecting cables to the chassis power supplies Removing the 8010co chassis bottom 312096-A bezel Location of power supplies Loosening the power supply retaining screws +DC -DC Power supply cables Attaching the positive lead +DC -DC Replacing the power supply Routing power supply cables to the BIP Labeling cables for the BIPConnecting the ground cables to the rack grounding strip Rack grounding strip exampleConnecting the power supply cables to the BIP Attaching power supply cable leads to the BIPLocate the BIP ground cable see on Attaching the BIP ground cable Connecting DC input power feeds to the BIP B feed example Single chassis and dual chassis input optionsLocating the a and B -48 VDC input feeds Connecting the a and B -48 VDC input feeds to the BIP 1 Connecting the a and B -48 VDC input feeds to the BIP 2 Connecting the A/B input feed returns 1 Go to the next section, Replacing covers on Replacing covers Replacing the plastic back cover on the BIPGo to the next section, Installing shelf alarm cables on Installing shelf alarm cables Installing shelf alarm cablesVerifying the installation Initial power-up Verifying the LEDsPowering off the system Installation Installation Rev Chapter Problem solving Problem solving Interpreting the LEDsOr a problem in circuits that are not essential to Diagnosing and correcting the problem Corrective actions Corrective actionsProblem solving Corrective actions Appendix a Technical specifications EnvironmentalAppendix a Technical specifications Physical dimensionsSafety agency certification ElectricalShelf alarm connectors J1 and J2 Appendix B BIP external cable pin assignmentsJ1 and J2 shelf alarm connector pin assignments Appendix B BIP external cable pin assignmentsOffice alarm connectors J3 and J4 J3 and J4 high-density 26-pin D-sub connectorJ3 and J4 office alarm connector pin assignments Standalone office alarm connector J5 J5 high-density 26-pin D-sub connectorJ5 standalone office alarm connector pin assignments Index NumbersIndex