48Chapter 2 Installation
5Route the remaining (black) power supply cables from the back of the lower and upper shelf chassis to the back panel of the BIP, loosely fastening them with
6Loosely support the power supply cables with
7Proceed to, “Connecting the ground cables to the rack grounding strip.”
Connecting the ground cables to the rack grounding strip
To connect the power supply ground cables to the rack grounding strip:
1Locate the rack grounding strip at the back base of the rack (Figure 31).
Note: Figure 31 shows an example of a rack grounding strip. Your rack grounding strip can look different than the one shown in this example.
2Attach the lug ends of the power supply ground cables to the rack grounding strip (Figure 31).
Use a
Figure 31 Rack grounding strip example
1
2
3
4
1 | = Hex head bolt | 3 | = Ground crimp lug |
2 | = Lock washer | 4 | = Rack grounding strip |
10433FA
3Proceed to “Connecting the power supply cables to the BIP” on page 49.