Programming XR-40CX or XR-60CX Dixell Electronic Controller
Reprinted with permission from Dixell.
The Dixell
The controller uses two levels of programming that can be accessed through the keypad. The first level is the user level. It gives access to six settings — temperature differential, defrost cycle intervals, defrost termination temperature, draining time, defrost fan delay and fan stop temperature.
The second level is the service level. It allows access to all other parameters. It is recommended that changes in this level be made only by a qualified technician.
Installation and Operations Manual
Front Panel Commands
Button Command
To display target set point; in programming mode it selects a parameter or confirm an operation
(DEF) To start a manual defrost
(UP): To see the max. stored temperature; in programming mode it browses
the parameter codes or increases the displayed value
(DOWN) To see the min stored temperature; in programming mode it browses the parameter codes or decreases the displayed value
To switch the instrument off, if onF = oFF
Not enabled
KEY COMBINATIONS
+To lock & unlock the keyboard
+To enter in programming mode
+To return to the room temperature display
Use of LEDs
LED | LED MODE | FUNCTION |
ON
Flashing
ON
Flashing
ON
Flashing
ON
ON
ON
°C/°FON
°C/°FFlashing
Compressor enabled
enabled
Defrost enabled
Drip time in progress
Fans enabled (XR60CX only)
Fans delay after defrost in progress (XR60CX only)
An alarm is occurring
Continuous cycle is running
Energy saving enabled
Measurement unit
Programming phase