PRO3 Side Mount Packaged Refrigeration System
Performance, Capacities and Specifications
Table 2 Model PST Cooler Application Air Defrost BTUH at 95°F Ambient Temperature
Model
Box Temperature
35°F | 38°F |
Voltage
MCA
MOPD
Evaporator CFM
Dimensions
Figure
PST070H6B* | 6,641 | 6,968 | 15 | 20 | 625 | A | |
PST090H6B* | 8,643 | 9,064 | 15 | 20 | 625 | A | |
PST131H6B* | 12,448 | 13,107 | 15 | 20 | 1,350 | B | |
PST147H6B* | 14,081 | 14,758 | 15 | 20 | 1,350 | B |
Table 3 Model PST Cooler Application Electric Defrost BTUH at 95°F ambient temperature
Model
35°F Box Temperature
Voltage
MCA
MOPD
Evaporator
CFM
Dimensions
Figure
PST066M6B* | 6,641 | 15 | 20 | 625 | A | |
PST086M6B* | 8,643 | 15 | 20 | 625 | A | |
PST124M6B* | 12,448 | 15 | 20 | 1,350 | B | |
PST141M6B* | 14,081 | 15 | 20 | 1,350 | B |
Table 4 Model PST Freezer Application Electric Defrost BTUH at 95°F ambient temperature
Model
Box Temperature
0°F |
Voltage
MCA
MOPD
Evaporator
CFM
Dimensions
Figure
PST034L6B* | 4,746 | 3,444 | 2,260 | 15.0 | 20 | 625 | A | |
PST051L6B* | 6,530 | 5,121 | 3,720 | 15.0 | 20 | 625 | A | |
PST057L6B* | 7,541 | 5,735 | 3,918 | 15.0 | 20 | 1,350 | B | |
PST077L6B* | 10,002 | 7,716 | 5,689 | 20.7 | 35 | 1,350 | B |
Table 5 Model PST Specifications
Model
Refrigerant
Refrigerant Charge (oz.)
Approximate Net Weight
lbs. | kg |
|
|
Coolers |
|
|
|
|
PST070H6B* | 36 | 260 | 118 | |
PST090H6B* | 36 | 265 | 120 | |
PST131H6B* | 40 | 320 | 145 | |
PST147H6B* | 40 | 325 | 148 | |
Coolers with electric defrost |
|
|
| |
PST066M6B* | 36 | 260 | 118 | |
PST086M6B* | 36 | 265 | 120 | |
PST124M6B* | 40 | 320 | 145 | |
PST141M6B* | 40 | 325 | 148 | |
Freezers |
|
|
|
|
PST034L6B* | 36 | 260 | 118 | |
PST051L6B* | 36 | 265 | 120 | |
PST057L6B* | 40 | 320 | 145 | |
PST077L6B* | 40 | 325 | 148 |
* H for PSC, E for EC motor on evaporator section only.
WARNING: This equipment may contain a substance that harms public health and the environment by destroying ozone in the upper atmosphere. Venting of certain refrigerants to the atmosphere may be illegal in your location. Refrigerant recovery devices should be used when installing or servicing this product. Consult your local codes for requirements in your location.
WARNING: Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly. Failure to follow this warning may result in personal injury or death.
PRO3 Side Mount Packaged Refrigeration System Installation and Operations Manual, May 2008 | 19 |