Alarm Signals
Message | Cause | Outputs | |
P1 | Room probe failure | Compressor output according | |
to parameters “Con” and “COF” | |||
|
|
| |
P2 | Evaporator probe | Defrost end is timed | |
failure | |||
|
| ||
|
|
| |
P3 | Third probe failure | Outputs unchanged | |
|
|
| |
P4 | Fourth probe | Outputs unchanged | |
failure | |||
|
| ||
|
|
| |
HA | Maximum | Outputs unchanged | |
temperature alarm | |||
|
| ||
|
|
| |
LA | Minimum | Outputs unchanged | |
temperature alarm | |||
|
| ||
|
|
| |
HA2 | Condenser high | It depends on the Ac2 | |
temperature | parameter | ||
| |||
|
|
| |
LA2 | Condenser low | It depends on the bLL | |
temperature | parameter | ||
| |||
|
|
| |
dA | Door open | Compressor and fans restarts | |
|
|
| |
EA | External alarm | Output unchanged | |
|
|
|
Alarm Recovery
Probe alarms P1, P2, P3 and P4 start some seconds after the fault in the related probe; they automatically stop some seconds after the probe restarts normal operation. Check connections before replacing the probe.
Temperature alarms HA, LA, HA2 and LA2 automatically stop as soon as the temperature returns to normal values.
Other Messages
Message | Meaning | |
Pon | Keyboard unlocked | |
PoF | Keyboard locked | |
noP | In programming mode: none parameter is present in Pr1 | |
On the display the selected probe is not enabled | ||
| ||
noA | None alarm is recorded |
Installation and Operations Manual
Technical Data
Characteristic | Description |
Housing | self extinguishing ABS |
|
|
Case | XR40CX/XR60CX frontal 32x74 mm; |
| depth 60mm |
Mounting | XR40CX/XR60CX panel mounting in a |
| 71x29mm panel |
|
|
Protection | IP20 |
Frontal protection | XR40CX/XR60CX IP65 |
|
|
Connections | Screw terminal block ≤ 2,5 mm2 wiring |
|
|
Power supply | according to the model: 12Vac/dc, |
| ±10%; 24Vac/dc, ±10%; 230Vac ±10%, |
| 50/60Hz, 110Vac ±10%, 50/60Hz |
|
|
Power absorption | 3VA max |
Display | 3 digits, red LED, 14,2 mm high; |
|
|
Inputs | Up to 4 NTC or PTC probes |
|
|
Digital input | free voltage contact |
Relay outputs | compressor: SPST 8(3) A, 250Vac; SPST |
| 16(6)A 250Vac or 20(8)A 250Vac |
| defrost: SPDT 8(3) A, 250Vac |
| fan (XR60CX only): SPST 8(3) A, 250Vac |
| or SPST 5(2) A |
|
|
Data storing | on the |
Kind of action | 1B |
|
|
Pollution grade | 2 |
|
|
Software class | A |
Rated impulsive voltage | 2500V |
|
|
Overvoltage Category | II |
|
|
Operating temperature | 0÷60 °C |
Storage temperature | |
|
|
Relative humidity | 20÷85% (no condensing) |
|
|
Measuring and | NTC probe: |
regulation range | PTC probe: |
| |
|
|
Resolution | 0,1 °C or 1°C or 1 °F (selectable) |
|
|
Accuracy (ambient | ±0,7 °C ±1 digit |
temp. 25°C) |
|
|
|