6.5.4 Transmitter Device Status Registers

The following are the values for the Device Status holding registers. These registers are bit field registers represented as a 32-bit floating point values for Transmitters.

Value

Transmitter Device Status

1

Transmitter Online

2

Low Battery Condition

► 4

Alarm Condition (WN571 only)

8

Sensor Error Condition

16

Sensor Overrange Condition

32

System Error Condition

64

Switch Input 1 Closed

128

Switch Input 2 Closed

► 256

Sq. Root Funct. (Diff. Pressure only - see

 

below)

Again, like Section 6.4.3, the status can be resolved by subtracting the largest number listed above from the value received from the holding register, and then subtracting the next highest and so on until the result is 0. Each of the values used indicate the respective condition listed above.

For example, the holding register reads 9, then subtract 8 and get 1. Then subtract 1 from 1 and get 0. Thus from the list above, we have a Sensor Error Condition and the Transmitter is online.

6.6Square Root Function

The Square Root Function only works with the Differential Pressure Transmitter. When the DP Transmitter is in Orifice mode, a Square Root calculation is performed. You have the option to display the Square Root Calculation. If this option is enabled, it will be displayed as Percent Square Root in WMT and sent to a Modbus Register.

The Square Root Calculation must be enabled through WMT. To display the Square Root Calculation, first open the Configuration dialog box for the DP Transmitter and select the Operation Mode tab. Make sure you have selected Orifice Flow from the mode menu. Then, from the Flow Units drop-down list, select Percent - Vol Flow. If the Density check box is selected, then Percent - Mass Flow can also be selected from the Flow Units drop-down list to show the Square Root Calculation.

33

Page 40
Image 40
Honeywell XYR 5000 LINE manual Square Root Function, Transmitter Device Status Registers, Value Transmitter Device Status