3.2.6.1Daisy-Chaining Power to Multiple Base Radios

A consideration when daisy-chaining power to multiple Base Radios is the power draw at power supply. Each Base Radio will typically draw 200mA @ 24VDC. This means a single Base Radio will draw a typical average power of 4.2W.

If using the supplied DIN rail mounted 15W power, it is suggested that no more than three Base Radios be tied parallel to this supply.

To daisy-chain two or more Base Radios together, each Base Radio should be wired in parallel to the next while making sure power is not supplied from two separate supplies to any single Base Radio. A typical wiring setup is shown in Figure 3-7below:

Power Supply

Base Radio 1

GND 24V B A

 

 

GND 24V B A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Base Radio 2

GND 24V B A

GND 24V B A

Figure 3-7 Daisy-Chaining Power to Multiple Base Radios

3.2.6.2Daisy-Chaining RS-485 to Multiple Base Radios

Modbus connections can be daisy-chained together, but WMT connections cannot. There can only be one Base Radio, multiple Output Modules, and a PC on the same WMT RS- 485. If you have two Base Radios connected to a PC running WMT, you must have two COM ports.

13

Page 20
Image 20
Honeywell XYR 5000 LINE manual Daisy-Chaining Power to Multiple Base Radios, Daisy-Chaining RS-485 to Multiple Base Radios