total from the subtraction and subtract the next largest number possible and so on until the result is zero. Each value that was used in the subtraction indicates that the Transmitter is online.

For example: The On/Offline Status holding register contains the value 15. In this case the largest value we can subtract is 8, which leaves a result of 7. Now we can subtract 4 from 7 and get 3. Now subtract 2 from 3 and we get 1. Finally we subtract 1 from 1 and get 0, so we are done. Which Transmitters are online? We subtracted 8,4,2 and 1, and these numbers correspond to Transmitters’ with RF IDs 1,2,3 and 4.

Note An alternate method to determining which Transmitter(s) are online is to look at the Base Radio Holding Register as a binary number with the rightmost bit representing Transmitter 1 and the leftmost bit representing Transmitter 16. For example, the binary representation for Transmitters 1-4 online is as follows:

0000000000001111

In another example, say the On/Offline Status holding register contains the value 6. We can subtract 4 to get 2. Then we can subtract 2 to get 0. Thus Transmitter 2 and 3 are online, but Transmitters 1 and 4 are offline.

6.5Transmitter Holding Registers

The following are the Transmitter holding registers when used in the Device ID Mapping Mode (First Table) and the Register Mapping Mode (Second Table).

6.5.1 Device ID Mapping Mode

 

Transmitter Holding

 

Device ID =

 

 

Registers

 

Base Radio Modbus ID + RF ID

 

 

(DEVMODE Only)

 

 

 

 

Register Address

 

Description

Register Type

 

00001

 

Device Type

32-Bit IEEE

 

00002

 

Device Type

Floating Point

 

00003

 

Device Status

32-Bit IEEE

 

00004

 

Device Status

Floating Point

 

00005

 

Primary Sensor Value

32-Bit IEEE

 

00006

 

Primary Sensor Value

Floating Point

 

00007

 

Secondary Sensor Value

32-Bit IEEE

 

00008

 

Secondary Sensor Value

Floating Point

 

00009

 

Tertiary Sensor Value

32-Bit IEEE

 

00010

 

Tertiary Sensor Value

Floating Point

6.5.2 Register Mapping Mode

 

 

 

 

 

 

 

Transmitter Holding

 

Device ID =

 

 

Registers

 

Base Radio Modbus ID

 

 

(REGMODE Only)

 

 

 

 

Register Address

 

Description

Register Type

 

00001 + (RF ID * 10)

 

Device Type

32-Bit IEEE

 

00002 + (RF ID * 10)

 

Device Type

Floating Point

 

00003 + (RF ID * 10)

 

Device Status

32-Bit IEEE

 

00004 + (RF ID * 10)

 

Device Status

Floating Point

31

 

 

 

 